< ORDER >
1. Prepare Manifold, refrigerant and scale. (sold separately)
2. Connect Manifold to refrigerant charging port As shown in the figure above.
3. Connect Manifold and refrigerant.
4. Perform the air purge between Manifold hose.
5. When is displayed, open the valve and fill the system with the refrigerant.
4.4 Refrigerant charging method and error contents
• Install refrigerant charging device like this page.
• If it is out of the guarantee temperature range, can end by not operating refrigerant charging.
- Outdoor guarantee temperature range (cooling : 0~43℃, heating : -10~24℃)
- Indoor guarantee temperature range (cooling : 18~32℃, heating : 10~27℃)
• If the system are turned off continuously by low pressure decrease excessively due to refrigerant lack before E10 expres-
sion, try again after add about 15% refrigerant of regular refrigerant amount.
• Press SW04C(X: Cancel) button and down dip switch after function end.
Gas pipe
Liquid pipe
Refrigerant
Scales
Manifold
CAUTION
1. When you put refrigerant, using the specified equipment.
2. Please the wired remote control to set the main unit.
3. During Indoor unit operating, be careful not to be Thermo off.
4. If The Outdoor unit occurred frost when Heating automatic refrigerant filling,
Please restart corresponding function after forced defrost.
WARNING
• When perform the leakage test and air purge, please use a vacuum pump or an inert gas. (nitrogen)
If you use Oxygen, compressed air and flammable gas, there are fire and danger of explosion.
There are risk of death, personal injury, fire, explosion.
Function