2.11 Reverse Valve
2.12 Temperature Sensor
1. Keep it off before the outdoor unit is powered on and the indoor unit is turned on.
2. Cooling, defrosting, oil recovery : OFF, heating : ON
3. When alternating cooling to heating, transform 4 way valve during re-starting for 3 minutes.
4. To check the mode of cooling/heating operation of 4 way valve, touch the piping surface of low pressure service valve.
5. Refrigerant flowchart of 4 way valve
6. Insulation resistance in the state of connecting the valve to coil should be over 100mΩ when measure it with DC
mega tester(DC 500V).
1) outdoor temperature sensor : TH1
2) Pipe temperature sensor : TH2
3) Discharge pipe(D-pipe) temperature sensor : TH3
1. Check the condition of installation and the contact of temperature sensor.
2. Check whether the connector contact of temperature sensor is normal.
3. Measure the resistance of temperature sensor.
Resistance
TH1
10KΩ±1%(25℃)
1.07KΩ±3.3%(85℃)
5KΩ±1%(25℃)
535KΩ±3.3%(85℃)
200KΩ±1%(25℃)
28KΩ±7.7%(85℃)
TH2
TH3
[Heating Operation]
Outdoor Heat
Exchanger
Outdoor Heat
Exchanger
D : Discharge
E : Evaporator
C : Condensor
S : Suction
Indoor Heat
Exchanger
[Cooling Operation]
Checking Method for Key Components