- 24 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Function
2.4 Stopping operation
2.4.1 Stopping operation on cooling mode
-
-
-
-
Note
OFF
Stop
OFF
Operation
4way valve
Subcooling EEV
Main EEV
FAN
Inv Compressor
Component
OFF over 30°C air temperature
Stop(Min. pulse)
-
-
-
Note
ON
Stop
OFF
Operation
4way valve
Subcooling EEV
Main EEV
FAN
Inv Compressor
Component
16 pulse
32 pulse
16 pulse
32 pulse
Stop(Min. pulse)
When oil level which is measured by oil level sensor is kept differently between each compressor then oil
equalizing EEV will be open during 5 minutes.
This function prevent oil unbalance between inverter. compressor.
2.5 Oil equalizing control
2.4.2 Stopping operation on heating mode
Содержание ARNU05GL1G2
Страница 138: ...P NO MFL67369002 April 2013 ...