Troubleshooting Guide
- 114 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
59*
Master 591
Slave1 592
Slave2 593
Slave3 594
Series Installation
Error
Error
No.
Error Type
Error Point
Main Reasons
Series Installation of Slave
Outdoor Unit Larger Than
Master Capacity
1. Dip Switch Setting Error
n
Error Diagnosis and Countermeasure Flow Chart
Is Dip switch
setting normal?
Is there any error when
power reset?
Recheck installation
condition
Are there setting with
Master
→
Slave1
→
Slave2
→
Slaver3?
No
No
No
Yes
Yes
Yes
1. Set the most
capacitor
ODU for Master
Set with Master
→
Slave1
→
Slave2
→
Slaver3
1. Replace Main PCB
* Dip Switch Setting
Slave1
Slave2
Slave3
1
2
3
4
5
6
7
ON
1
2
3
4
5
6
7
1
2
3
4
5
6
7
ON
1
2
3
4
5
6
7
1
2
3
4
5
6
7
ON
1
2
3
4
5
6
7