Display
Title
Cause of Error
Outdoor unit related error
5 1 1 Excessive capacity of indoor units
Excessive connection of indoor units compared to
capacity of Outdoor Unit
5 2
1
Communication error : inverter PCB
’
Main PCB
Failing to receive inverter signal at main PCB of
Master Outdoor Unit
2
Communication error : inverter PCB
’
Main PCB
Failing to receive inverter signal at main PCB of
Slave1 Outdoor Unit
3
Communication error : inverter PCB
’
Main PCB
Failing to receive inverter signal at main PCB of
Slave2 Outdoor Unit
4
Communication error : inverter PCB
’
Main PCB
Failing to receive inverter signal at main PCB of
Slave3 Outdoor Unit
5 3 1
Communication error : indoor unit
’
Main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of
Outdoor Unit .
5 7
1
Communication error : Main PCB
’
inverter PCB
Failing to receive signal main PCB at inverter PCB of
Master Outdoor Unit
2
Communication error : Main PCB
’
inverter PCB
Failing to receive signal main PCB at inverter PCB of
Slave1 Outdoor Unit
3
Communication error : Main PCB
’
inverter PCB
Failing to receive signal main PCB at inverter PCB of
Slave2 Outdoor Unit
4
Communication error : Main PCB
’
inverter PCB
Failing to receive signal main PCB at inverter PCB of
Slave3 Outdoor Unit
5 9 1
Mixing Installation of Sub Outdoor
Unit
Mixing Installation of Old Sub Outdoor Unit and New
Slave Outdoor Unit
6 0
1
Inverter PCB EEPROM Error of
Master Outdoor Unit
Access Error of Inverter PCB of Master Outdoor Unit
2
Inverter PCB EEPROM Error of
Slave1 Unit
Access Error of Inverter PCB of Slave1 Outdoor Unit
3
Inverter PCB EEPROM Error of
Slave2 Unit
Access Error of Inverter PCB of Slave2 Outdoor Unit
4
Inverter PCB EEPROM Error of
Slave3 Unit
Access Error of Inverter PCB of Slave3 Outdoor Unit
6 2
1
Master Outdoor Unit Inverter
Heatsink High Temperature
System is turned off by Master Outdoor Unit Inverter
Heatsink High Temperature
2
Slave1 Outdoor Unit Inverter
Heatsink High Temperature
System is turned off by Slave1 Outdoor Unit Inverter
Heatsink High Temperature
3
Slave2 Outdoor Unit Inverter
Heatsink High Temperature
System is turned off by Slave2 Outdoor Unit Inverter
Heatsink High Temperature
4
Slave3 Outdoor Unit Inverter
Heatsink High Temperature
System is turned off by Slave3 Outdoor Unit Inverter
Heatsink High Temperature
Self-diagnosis function