ENGLISH
1. Select space for installing the unit, which will meet the following conditions:
The place where the unit shall be installed inside.
The place shall easily bear a load exceeding four times of the unit weight.
The place where the unit shall be leveled.
The place shall allow easy water drainage.
The place where the unit shall be connected to the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where there should not be any heat source or steam near the unit.
Installation Space
• The following values are the least space for installation.
If any service area is needed for service according to field circumstance, obtain enough service
space.
• The unit of values is mm(inch).
(Unit: mm(inch))
100(3-15/16)
100(3-15/16)
100(3-15/16)
100(3-15/16)
Base pad
200(7-7/8)
631(24-16/19)
631(24-16/19)
H-Beam supporter
Concrete supporter
(Unit: mm(inch))
Service space
(front side)
Piping space
(front side)
Product
520(20-17/36)
100
(3 ‐15/16)
100
(3 ‐15/16)
400(15-3/4)
330(13)
600(23-5/8)
(Anti-vibration material)
Selection of the best location