![LG ARNH963K2A2 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/lg/arnh963k2a2/arnh963k2a2_installation-manual_213303027.webp)
Accessories Installation
Hydro Kit
Installation Manual
27
ENGLISH
Water tank temperature sensor Connection
• Select the suitable pump by referring to the flow rate table with water
temperature difference between the entrance and the exit.
• It is recommended that the flow rate is Rated water flow (refer to the
specification of PDB)
• Select a correctly sized pump capable of delivering required flow rate at the
static head pressure of the system piping and
Hydro Kit
.
• Select a suitable relay for pump capacity when connecting the pump to the
unit.
• Connect the relay to terminals 11 and 12 located in the
Hydro Kit
control
box.
• Connect the domestic hot water tank sensor to PCBʻCN-TH4ʼ socket
(red).
11
12
L
N
Pump
(main)
Relay
Pump
Water tank
thermistor
Housing
CN-TH4
CAUTION:
• Make sure to supply external power with the pump.
CAUTION:
• If water tank temperature sensor is not connected, error will occur.
(CH08) Sensor not required for dedicated radiant or hydronic heating applications.
Water Pump Interlock Wiring (Filed Provided)