System Set-Up
Hydro Kit
Installation Manual
49
ENGLISH
• Function Code 30 :
Remote Controller Program Version
Display Remote Controller Program Version.
Th On
Th Off
0
-0.5°C(-0.9℉)
1.5°C(2.7℉)
1
4°C(7.2℉)
6°C(10.8℉)
2
2°C(3.6℉)
4°C(7.2℉)
3
-1°C(‐1.8℉)
1°C(1.8℉)
2E : Room Air temperature
Th On
Th Off
0
-2°C(- 3.6℉)
2°C(3.6℉)
1
-6°C( ‐10.8℉)
4°C(7.2℉)
2
-2°C(‐3.6℉)
4°C(7.2℉)
3
-1°C(‐1.8℉)
1°C(1.8℉)
2F : Leaving Water temperature and
Domestic Hot Water (DHW) temperature
• Function Code 2B
: Setting Domestic Hot Water heating timers
Determine time duration : Operation time and stop time of Domestic Hot Water tank heating
- Value #1 of Function Code 2B : This time duration defines how long Domestic Hot Water
tank heating can be continued.
- Value #2 of Function Code 2B : This time duration defines how long Domestic Hot Water
tank heating can be stopped. It is also regarded as time
gap between Domestic Hot Water tank heating cycle.
- Example of timing chart :
• Function Code 2C :
Setting water flow rate
Determine the difference between target inlet water temperature and target outlet water
temperature from water flow rate.
- Value #1 of Function Code 2C : Water flow rate which flows to
Hydro Kit
.
• Function Code 2E and 2F :
Changing thermal on/off temperature
Select Thermal on/off Temperature gap.
Domestic Hot Water tank
heating is enabled
Domestic Hot Water tank
heating is required
Domestic Hot Water tank
heating operation
Time
2B.01
2B.01
2B.02
2B.02
2B.02
Setting value
Water flow rate (l/min)
ARNH963K2A2
50
45~50
55
51~55
60
56~60
65
61~65
70
66~70
75
71~75
80
76~80
85
81~85
90
86~90
92
91~92