![LG ARNH963K2A2 Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/lg/arnh963k2a2/arnh963k2a2_installation-manual_213303014.webp)
Installation
14
Hydro Kit
Strainer
- Use the 50 mesh strainer.
(Exclude scale diameter of 0.4mm or less and other net)
- Check the strainer direction and assemble on the inlet hole (Refer to picture)
- Wrap the Teflon tape on the screw thread of the water pipe for more than 15 times for assembly.
- Install the service port facing downward. (Within left/right 45 degrees)
- Check if there is any leakage on the connecting part.
- Clean the strainer.
Water In
Strainer
Side
Front
45°