33
Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL SYSTEM
Figure 21: UI Module.
Table 16: UI Module Component Details.
Drawing
Reference
Label
Unit Connection
Type
Position Indicates
Range
2
CH1
CH1 port of Other module for communication
RS-485
3
DI1
Occupancy
NO (Closed = Occupied)
DI2
Supply Air filter Switch
NO (Closed = Dirty)
DI3
Return Air filter Switch (Field Option)
NO (Closed = Dirty)
4
UI1
Unassigned
UI2
Unassigned
UI3
Unassigned
UI4
Unassigned
UI5
Space / Return Duct Temperature (Field Option)
0 – 10Vdc
-130-210°F
UI6
Space / Return Duct Relative Humidity (Field Option)
0 – 10Vdc
-130-210°F
Terminal Connections for Electrical Components
UI Module