PRE-COMMISSIONING
Ambient Conditions and the Leak / Pressure Check
If the ambient temperature changed between the time when pressure was applied and when the pressure drop was checked, adjust
results by factoring in approximately 0.79 psi for each 1°F of temperature difference.
Correction formula: (°F Temperature when pressure was applied - °F Temperature when pressure drop was checked) x 0.79.
Example: When pressure (550 psig) was applied, temperature was 80°F; 24 hours later when pressure drop (540 psig) was checked,
temperature was 68°F.
Thus, (80°F - 68°F) x 0.79 = 9.5 psig.
In this case, the pressure drop of 9.5 psig was due to temperature differences, therefore, there is no leak in the refrigerant piping system.
The bubble solution must be a solution designed for refrigerant leak testing. Common soap solution must
never be used on refrigerant piping as
those contain chemicals that could corrode copper and brass, and cause product malfunction.
7. If the pressure does NOT drop for 24 hours, the system passes the test. See how ambient conditions will affect the pressure test below.
8. If the pressure drops and it is not due to ambient conditions, there is a leak and it must be found. Remove the bubble solution with a clean
cloth, repair the leak(s), and perform the leak / pressure check again.
9. After the system has been thoroughly tested and no leaks are found, depressurize by loosening the charging hose connector at the nitro-
gen cylinder regulator. When system pressure returns to normal, completely disconnect the charging hose from the cylinder, and release
the nitrogen charge from all refrigerant piping. Wipe off any remaining bubble solution with a clean cloth.
Figure 24: Leak / Pressure Test for a System Designed with a Split Compact DOAS Unit.
Farthest Sub outdoor unit is the Sub outdoor unit installed farthest away from the refrigerant
piping system / DOAS unit.
Triple Leak / Pressure Check
Main Outdoor Unit
Farthest Sub Outdoor Unit