BACnet / Modbus Points List
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
%$&1(702'%8632,176/,67
Variable
Description
Active
Text
Inactive
Text
BACnet
Modbus
Access
COV
Incre. Index
Register
Type Size
x 0.1
Req.
,QSXW5HJLVWHUFRQWLQXHG
I9154_Slave#1_ DOAS_HRUnit_LiquidTemp
Sub #1 DOAS Liquid
Pipe Refrigerant
Temperature
Read_NoWrite
39155 Input
2
ż
I9155_Slave#1_ DOAS_HRUnit_SCInletTemp
Sub #1 DOAS Sub-
Cooling Circuit Inlet
Temperature
Read_NoWrite
39156 Input
2
ż
I9156_Slave#1_ DOAS_HRUnit_
SCOutletTemp
Sub #1 DOAS Sub-
Cooling Circuit Outlet
Temperature
Read_NoWrite
39157 Input
2
ż
+ROGLQJ5HJLVWHU
H000_ModbusSlaveAddress
DOAS Unit No. (Multiple
Combination of DOAS
unit)
Read_NoWrite
40001 Holding 2
H010_OverrideKeepTime
Manual Override Holding
Time
Read_NoWrite
40011 Holding 2
H042_SATempSetpointOfTemperatureControl
Target temperature
[Supply air temperature
Control]
ReadCOV_
Commandable 0.5 40043 Holding 2
ż
H044_
HeatingCoolingDeadBandOfTemperatureControl
Dead band
Read_NoWrite
40045 Holding 2
ż
'LVFUHWH,QSXW
D000_OperationStatus
DOAS Status
Read_NoWrite
10001 Discrete
D001_ErrorStatus
Error Status
Read_NoWrite
10002 Discrete
D002_AlarmStatus
Alarm status of DOAS
and ODU
Read_NoWrite
10003 Discrete
D016_SAFanStatus
Status of Supply Fan
On/off
Read_NoWrite
10017 Discrete
D017_EAFanStatus
Status of Supply Fan
On/off
Read_NoWrite
10018 Discrete
D018_ERWStatus
Status of Energy
Recovery Wheel On/off
Read_NoWrite
10019 Discrete
D019_PreheatHeater
Status of Electric Pre-
Heater On/off
Read_NoWrite
10020 Discrete
D020_MainCoilStatus
Status of On/Off
Read_NoWrite
10021 Discrete
D021_ReheatCoilStatus
Reheat Coil EEV
Opening position (pulse)
Read_NoWrite
10022 Discrete
D022_RecoveryCoilStatus
Reheat Coil EEV
Opening position (pulse)
Read_NoWrite
10023 Discrete
D030_SAFilterSign
Supply Air Filter Alarm
Read_NoWrite
10031 Discrete
D031_RAFilterSign
Return Air Filter Alarm
Read_NoWrite
10032 Discrete
D032_Occupancy
Occupancy Status
(Occupied / Unoccupied)
Read_NoWrite
10033 Discrete
D046_LatentHeatControlOperCondition
Soft Shutdown setpoint
Read_NoWrite
10047 Discrete
D047_AutoDryOperCondition
Auto Dry Operation
(Time Delay)
Read_NoWrite
10048 Discrete
Coil
C000_UnitEnable
Unit Enable
Enabled Disabled
ReadCOV_
Commandable
1
Coil
C001_Occupancy
Unit Occupancy
Occupied Unoccupied
Read_
Commandable
2
Coil
Table 29: BACnet / Modbus Points List for DOAS Units Table, continued.