84
ENGLISH
USING THE PROGRAM
4.
Select the program type.
Item
Description
Event Log Only
Normal device interface program
Group Clone
Program to copy input setting and apply to output
Alarm ACK
Required
Device control program for emergency situation
Permit User
Control
Set priority of Interlocking. If ‘Permit User Control’ is checked, Just control
output device once when input condition is satisfied. If it is not checked,
always interlocking function takes priority.
User control
permission
Set up the priority of device linkage control. When checked, under the
status which meets the input device condition, controlling the output device
is made just once, and after that, when the user takes the control, user
control has the priority. When not checked, device linkage control always
has the priority.
NOTES
y
For device interface control, chiller and some AHU(Modular Fresh Air, Modular Heat Recovery,
DOAS) cannot be registered.
y
When it is set to emergency program, if the corresponding conditions are met, it is recognized
as emergency situation, and other control signals are blocked. For details on emergency
situation occurrences, refer to
Emergency situation occurrence and reset
.
y
You can set only 1 emergency program.
Содержание ACP IV ACP
Страница 2: ......
Страница 8: ...vi ENGLISH MEMO ...
Страница 20: ...12 ENGLISH MEMO ...
Страница 181: ...ver 1 0 0 ...