38
ENGLISH
USING THE PROGRAM
Air-cooled scroll chiller, water-cooled scroll chiller
Air-cooled and water-cooled is separated according to the refrigerant (cooling in air: air, liquid-
cooled: water). Functions and menus are the same, but there is a difference in the range and set
temperature, etc.
The following menu controls the configuration and function of the air-cooled scroll chiller, water-
cooled scroll chiller.
Item
Description
Operation
y
[ON]
Button: Starts the operation of the device.
y
[OFF]
Button: Stops the operation of the device.
GoTo
y
[Schedule
▶
]
Button: Move to Schedule menu.
y
[View Details
▶
]
button: Moves to detail information screen.
Mode
y
[COOL]
Button: Operates with Cooling Mode.
y
[HEAT]
Button: Operates with Heating Mode.
Mode Target
Temp (
℃
)
Click(Touch)
[▲]
/
[▼]
to set the mode set temperature.
y
Air-cooled scroll chiller
-
COOL: 5
℃
~15
℃
-
HEAT: 35
℃
~55
℃
y
water-cooled scroll chiller
-
COOL: 5
℃
~15
℃
-
HEAT: 40
℃
~57
℃
Demand limit
As measured at 1minute intervals the power consumption of the refrigerator,
the current power consumption does not exceed a target power consumption,
demand rate limit, function to lower the operation rate of the current.
Click(Touch) the
[▲]
/
[▼]
button to set a limit on the rate of demand.
y
air-cooled scroll chiller: 0~120 (10 units)
y
water-cooled scroll chiller: 0, 30~120 (10 units)
[Apply]
Button
Apply control menu setting to the device.
[Detail.
▶
]
Button Controls details.