USING THE PROGRAM
•
Indoor 2Setpoint (Auto Mode)
In the detail control window of the indoor unit, touch
[2Setpoint]
button, and in the displayed
automatic control setting window, you can set the automatic control. The composition and
functions of the automatic control menu are as follows.
Item
Description
Auto Change
Over
Set the auto change over function to switch the operation mode
automatically to keep the proper room temperature.
When Room Temp. > Upper, request Cool operation mode. When
Room Temp. < Lower, requests Heat operation mode. When Room
Temp. ≤ (Upper - Temperature difference) or Room Temp. ≥ (Lower +
Temperature differece), requests Fan operation mode.
(You can set up Temperature differernce in Environment > Advance
Setting > Temperature limit setting.) (The auto change over function
works well with "Heat Recovery" model. For other models, functionality
is limited.)
y
[ON]
Button: Enable Auto Change Over
y
[OFF]
Button: Disable Auto Change Over
Lower
Click(Touch)
[▲]
/
[▼]
to set the lower limit temperature range.
(18°C~30°C / 64°F~86°F).
Upper
Click(Touch)
[▲]
/
[▼]
to set the upper limit temperature range.
(18°C~30°C / 64°F~86°F).
Fan Speed
Set the fan speed to operates when auto change over function works.
When operation mode is COOL or HEAT, operates at user set fan
speed. And when operation mode is Fan, operates at low fan speed.