Troubleshooting Guide
98
Universal System Air Conditioner
9) Troubleshooting CH26
26
DC Compressor
Position
• Compressor
Starting fail error
• Check the connection of comp wire “U,V,W”
• Malfunction of compressor
• Check the component of “IPM”, detection parts.
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
1. Check the connection condition of PCB.
2. Check the connection condition of Comp. U,V,W wire.
3. Check the connection condition of CN_IPM(P), CN_IPM(N).
4. Check the comp resistor and insulation resistance .
5. Check the IPM.
6. Check the pressure of refrigerant.
7. Check the Service Valve Open.
Содержание ABNH366GLAC
Страница 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Страница 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Страница 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Страница 107: ...Electronic Control Device Service Manual 107 Main P C B ASM A 6871A10209 B 58 Ceiling Cacsette Type ...
Страница 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Страница 109: ...Electronic Control Device Service Manual 109 VK VL Series Ceiling Suspended ASM 6871A10025 ASM 6871A10186 ...
Страница 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Страница 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Страница 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Страница 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Страница 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Страница 116: ...Schematic Diagram 116 Universal System Air Conditioner G G N L N L C 3 C 2 C 4 C 1 Outdoor Unit ...
Страница 154: ...P No MFL30301501 Printed in Korea ...