Service Manual 75
Inverter SINGLE A
5. Electric Characteristics
Unit
Model
Type
MCA
MOP
MSC
RLA
kW
FLA
Voltage
Voltage range
Hz
Power
Compressor
OFM
AUUW368C1
[UU37WE]
AUUW368C
[UU37W UEC]
AUUW428C
[UU43W UHC]
AUUW488C
[UU49W UHC]
AUUW608C
[UU61W UHC]
7.76
21.1
14
7
0.13
1.4
9.12
26.0
14
7
0.18
1.5
10.99
29.7
14
7
0.18
1.5
11.00
35.0
14
7
0.18
1.5
inverter
50
380~415
Min : 352
Maxi :457
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the mini-
mum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Select proper circuit breaker as given below
MCA < circuit breaker
≤
MOP
6. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
7. MSC & RLA are measured as the compressor only test condi-
tion.
8. MSC values
14 : MSC of (inv. comp.)
9. RLA is measured during each individual compressor test condi-
tion.
Ex) 7.0 : RLA of (inv. comp.)
10. OFM is measured as the outdoor unit test condition
(Example) Selection of proper circuit breaker
Model : AUUH368C
- Rated running current : 5.09 A (refer to spec. sheet)
MCA = (1.25 x Load1) + Load2 + Load3
= (1.25 x 8.75) + 0 + (1.4) = 7.76 A
MOP = (2.25 x Load1) + Load2 + Load3
= (2.25 x 8.75) + 0 + (1.4) = 12.84 A
→
Finally select circuit breaker 20A
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Содержание ABNH366GLAC
Страница 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Страница 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Страница 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Страница 107: ...Electronic Control Device Service Manual 107 Main P C B ASM A 6871A10209 B 58 Ceiling Cacsette Type ...
Страница 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Страница 109: ...Electronic Control Device Service Manual 109 VK VL Series Ceiling Suspended ASM 6871A10025 ASM 6871A10186 ...
Страница 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Страница 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Страница 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Страница 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Страница 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Страница 116: ...Schematic Diagram 116 Universal System Air Conditioner G G N L N L C 3 C 2 C 4 C 1 Outdoor Unit ...
Страница 154: ...P No MFL30301501 Printed in Korea ...