Service Manual
77
Inverter SINGLE A
7. Installation
7.1 Select the best location
• If a roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the
condenser is not restricted.
• Do not place animals and plants in the path of the warm air.
• Take the air conditioner weight into account and select a place where noise and vibration are minimum.
• Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
• Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the
roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop
mounting.
• Ensure that the space around the back is more than 30cm and sides is more than 30cm. The front of the unit
should have more than 70cm of space.
More than
30cm
Fence or
obstacles
More than 70cm
More than 50cm
More than
More than
30cm
30cm
More than
30cm
Sunr
oof
More than 50cm
(Service space)
More than
30cm
Fence or
obstacles
More than 70cm
More than 50cm
More than
More than
30cm
30cm
More than
30cm
Sunr
oof
7.2 Settlement of outdoor unit
• Anchor the outdoor unit with a bolt and nut(ø10mm) tight-
ly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the
influence of wind and earthquake.
• In the case when the vibration of the unit is conveyed to
the hose, secure the unit with an anti-vibration rubber.
Bolt
Tubing connection
Caution:
Be very careful to carry product.
• Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are
dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children to death.
• When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support
may make outdoor unit unstable, resulting in a fall of it.
Содержание ABNH366GLAC
Страница 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Страница 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Страница 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Страница 107: ...Electronic Control Device Service Manual 107 Main P C B ASM A 6871A10209 B 58 Ceiling Cacsette Type ...
Страница 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Страница 109: ...Electronic Control Device Service Manual 109 VK VL Series Ceiling Suspended ASM 6871A10025 ASM 6871A10186 ...
Страница 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Страница 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Страница 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Страница 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Страница 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Страница 116: ...Schematic Diagram 116 Universal System Air Conditioner G G N L N L C 3 C 2 C 4 C 1 Outdoor Unit ...
Страница 154: ...P No MFL30301501 Printed in Korea ...