Heat Pump
50Hz/R410A
_
187
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
1.10 Electric characteristics
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the
minimum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25*RLA)+load1+load2
MOP = (2.25*RLA)+load1+load2
- Load1 : sum of current for all other motors
- Load2 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Select proper circuit breaker as given below
MCA < Circuit breaker ≤ MOP
6. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
7. MSC & RLA are measured as the compressor only test
condition.
8. MSC values
9. RLA is measured during each individual compressor test
condition.
10. OFM is measured as the outdoor unit test condition
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Unit
Power
Compressor
OFM
Model
Type
Hz
Voltage
Voltage range
MCA
MOP
RLA
KW
FLA
A2UW14GFA0
[MU2M15 UL2]
Inverter
50
220-240
MIN.:198
MAX.:264
9.4
16.7
7.3
0.04
0.25
A2UW16GFA0
[MU2M17 UL2]
9.4
16.7
7.3
0.04
0.25
A3UW18GFA0
[MU3M19 UE2]
12.8
22.5
9.7
0.09
0.59
A3UW21GFA0
[MU3M21 UE2]
13.5
23.8
10.3
0.09
0.59
A4UW24GFA0
[MU4M25 U42]
16.2
28.6
12.4
0.12
0.73
A4UW27GFA0
[MU4M27 U42]
16.5
29.1
12.6
0.12
0.73
A5UW30GFA0
[MU5M30 U42]
16.7
29.5
12.8
0.12
0.73
A5UW40GFA0
[MU5M40 UO2]
21.2
37.0
15.8
0.09 x 2
0.59 x 2
Содержание A4UW24GFA0
Страница 1: ...Heat pump 50Hz R410A 0CIM0 02E Replaces 0CIM0 02D ...
Страница 4: ...Part 1 General information 1 Model line up 2 Nomenclature 3 Appearance 4 Combination ...
Страница 290: ...BD Unit Distributor Box 1 Specifications 2 Dimensions 3 Piping Diagrams 4 Wiring Diagrams ...
Страница 367: ...Part 4 Special Part 1 Installation guide at the seaside 2 Seasonal wind and cautions in winter ...