2. Distributor type MULTI F DX (1 phase)
34
_ Heat pump
50Hz/R410A
Part 2 Product data_Outdoor units
2.9 Capacity coefficient factor
1) Rate of change in capacity due to the main piping length
Rate of change in cooling capacity
Rate of change in heating capacity
Main piping length rate of change in capacity
0
10
20
30
40
50
55
Main piping length(m)
70.0
75.0
80.0
85.0
90.0
95.0
100.0
Rate of change in capacity(%)
Heating capacity
Cooling capacity
5 10 15 20 25 30 35 40 45 50 55
100.0 98.8 97.3 95.8 94.3 92.8 91.3 89.8 88.3 86.8 85.3
Main piping length(m)
Rate of change
in cooling capacity(%)
5 10 15 20 25 30 35 40 45 50 55
100.0 99.6 99.2 98.7 98.3 97.8 97.4 96.9 96.5 96.0 95.6
Main piping length(m)
Rate of change
in heating capacity(%)