2. Guideline for each installation process
Part 3 Design and installation
2.8 Additional charge of refrigerant
2.8.1 Refrigerant charging instructions
①
The results of all calculations must be recorded. (make a list)
②
The refrigerant will need to be additionally charged when the distance between the outdoor Unit and the most distant
indoor unit is more than length (refer to section 8 outdoor unit installation condition)
③
The additional charging operation should be carried out by input of liquid into the liquid pipes from a charging cylinder fol-
lowing completion of the Vacuum drying operation.
④
When the additional charging operation cannot be satisfactorily completed , use the action of the compressor to com-
plete the additional charging during the test run.
R-410A is a non-azeotrope refrigerants. Therefore , these refrigerants must be charged in the Liquid state.
When charging the refrigerant into equipment from the cylinder , turn the refrigerant cylinder upside down.
Make sure that the refrigerant (liquid) is taken out from the bottom part of the refrigerant cylinder.
Do not take out the refrigerant (gas) at the upper of the refrigerant cylinder for charging.
NOTE
• Since some refrigerant cylinders differ in the internal mechanism, it is necessary to examine the cylinder carefully.
(Some cylinders have a siphon tube to eliminate the need for turning it upside down)
CAUTION
siphon tube
Refrigerant
cylinder
Outdoor unit A
Outdoor unit B
Refrigerant
cylinder
Содержание A4UW24GFA0
Страница 1: ...Heat pump 50Hz R410A 0CIM0 02E Replaces 0CIM0 02D ...
Страница 4: ...Part 1 General information 1 Model line up 2 Nomenclature 3 Appearance 4 Combination ...
Страница 290: ...BD Unit Distributor Box 1 Specifications 2 Dimensions 3 Piping Diagrams 4 Wiring Diagrams ...
Страница 367: ...Part 4 Special Part 1 Installation guide at the seaside 2 Seasonal wind and cautions in winter ...