3. Distributor type MULTI F DX (3 phase)
5
_ Heat pump
50Hz/R410A
Part 2 Product data_Outdoor units
3.4 Combination table
The individual indoor unit capacity can be calculated as follows depending on the total connected capacity of all indoor units.
Individual indoor unit
combinational capacity
[Q
idu(combi)
]
Outdoor unit rated capacity
[Q
odu(rated)
]
x –––––––––––––––––––––––––––––––––––––––––––
=
Individual indoor unit rated capacity [Q
idu(rated)
]
Total connected indoor unit rated capacity [Q
idu(rated)
]
Models : A7UW42LFA0 [FM41AH U32]
[Cooling capacity]
16
9,600
2.8
16,955
5.0
18,513
5.4
800
844
1,279
18
10,500
3.1
17,759
5.2
19,707
5.8
833
899
1,347
19
11,400
3.3
18,563
5.4
20,900
6.1
866
953
1,415
20
12,000
3.5
19,367
5.7
21,741
6.4
898
1,008
1,483
21
12,600
3.7
20,171
5.9
22,582
6.6
931
1,063
1,550
22
13,200
3.9
20,975
6.1
23,423
6.9
964
1,117
1,618
23
13,800
4.0
21,779
6.4
24,264
7.1
997
1,172
1,686
24
14,400
4.2
22,583
6.6
25,105
7.4
1,029
1,227
1,754
25
15,000
4.4
23,387
6.9
25,946
7.6
1,062
1,281
1,822
26
15,600
4.6
24,191
7.1
26,787
7.9
1,095
1,336
1,890
27
16,200
4.7
24,995
7.3
27,628
8.1
1,128
1,391
1,958
28
16,800
4.9
25,799
7.6
28,469
8.3
1,160
1,445
2,026
29
17,400
5.1
26,603
7.8
29,310
8.6
1,193
1,500
2,093
30
18,000
5.3
27,407
8.0
30,151
8.8
1,226
1,555
2,161
31
18,600
5.5
28,211
8.3
30,992
9.1
1,259
1,610
2,229
32
19,200
5.6
29,015
8.5
31,833
9.3
1,291
1,664
2,297
33
19,800
5.8
29,819
8.7
32,674
9.6
1,324
1,719
2,365
34
20,400
6.0
30,622
9.0
33,515
9.8
1,357
1,774
2,433
35
21,000
6.2
31,426
9.2
34,355
10.1
1,390
1,828
2,501
36
21,600
6.3
32,230
9.4
35,196
10.3
1,422
1,883
2,568
37
22,200
6.5
33,034
9.7
36,037
10.6
1,455
1,938
2,636
38
22,800
6.7
33,838
9.9
36,878
10.8
1,488
1,992
2,704
39
23,400
6.9
34,642
10.2
37,719
11.1
1,521
2,047
2,772
40
24,000
7.0
35,446
10.4
38,560
11.3
1,553
2,102
2,840
41
24,600
7.2
36,250
10.6
39,401
11.5
1,586
2,156
2,908
42
25,200
7.4
37,154
10.9
40,242
11.8
1,619
2,211
2,976
43
25,800
7.6
37,692
11.0
41,083
12.0
1,652
2,237
3,043
44
26,400
7.7
38,413
11.3
41,924
12.3
1,684
2,262
3,111
45
27,000
7.9
39,134
11.5
42,765
12.5
1,717
2,288
3,179
46
27,600
8.1
39,400
11.5
43,606
12.8
1,750
2,313
3,247
47
28,200
8.3
40,019
11.7
44,447
13.0
1,783
2,339
3,315
48
28,800
8.4
40,740
11.9
45,288
13.3
1,815
2,364
3,383
49
29,400
8.6
41,300
12.1
46,129
13.5
1,848
2,390
3,451
50
30,000
8.8
41,440
12.1
46,503
13.6
1,881
2,416
3,519
51
30,600
9.0
41,580
12.2
46,877
13.7
1,914
2,442
3,586
52
31,200
9.1
41,720
12.2
47,252
13.8
1,946
2,468
3,654
53
31,800
9.3
41,860
12.3
47,626
14.0
1,979
2,494
3,722
54
32,400
9.5
42,000
12.3
48,000
14.1
2,012
2,520
3,790
Total indoor unit
capacity
(kBtu/h)
Min
Cooling capacity
Rated
Max
Btu/h
kW
Btu/h
kW
Btu/h
kW
Min
Rated
Max
Input (W)
Note :
1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB
; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when oper-
ating frequency is constant.
Values for changes in capacity are fixed after accounting for variations in operating
frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 16~54 Btu/h(40%~130%)
5. At least two indoor units should be connected.
Example)
• Outdoor unit model : A7UW42LFA0 [FM41AH U32]
• Total indoor units combination : 7k + 9k + 9k + 9k + 9k = 43k
• Each indoor unit combinational capacity?
- Q
odu(rated)
: 10.9kW, Q
idu(rated)
: 43 k (Btu/h)
7 9
∴
Q
idu(combi
) : [7k] = 10.9kW x ––– = 1.77kW Q
idu(combi)
: [9k] = 10.9kW x –––– = 2.28kW
43 43
Содержание A4UW24GFA0
Страница 1: ...Heat pump 50Hz R410A 0CIM0 02E Replaces 0CIM0 02D ...
Страница 4: ...Part 1 General information 1 Model line up 2 Nomenclature 3 Appearance 4 Combination ...
Страница 290: ...BD Unit Distributor Box 1 Specifications 2 Dimensions 3 Piping Diagrams 4 Wiring Diagrams ...
Страница 367: ...Part 4 Special Part 1 Installation guide at the seaside 2 Seasonal wind and cautions in winter ...