Commissioning and configuration
Le
u
ze electronic
MA 255
i
6
3
TNT
35/7-2
4
V
12.3.2
Installation of the EDS file
The MA 255
i
is configured in the planning tool/control by means of the EDS file.
Install the EDS file corresponding to the MA 255
i
in your planning tool/the control
(e.g., RSNetWorx).
Notice!
You can find the EDS file at:
www.leuze.com -> Download -> identify-> Modular interfacing units.
If the MA 255
i
has been assigned an address in the planning tool, the address is to be set
on the MA 255
i
via the S1 and S2 address switches, see chapter 12.1 "Measures to be
performed prior to the initial commissioning", section "Set DeviceNet device address" on
page 59. Only if the addresses are the same between the MA 255
i
and the control can
communication be established.
12.3.3
Setting the parameters on the MA
Notice!
There are two options for changing the parameters of the MA: setting is either performed
on the DeviceNet master via the scan list (communication parameters), or setting is enabled
by temporarily removing the participants from the scan list. After successful parameter
change, the participant can be re-added to the scan list.
This is illustrated in the following screenshot from the RSNetWorx for DeviceNet
configuration tool: