Commissioning
➜
Connect data signal and power cables with the correct polarity.
Check the following points prior to commissioning.
·
All cable and plug connections.
·
Profibus interface settings (1)
·
- Baud rate (2) on both DDLS 170s:
Desired transmission rate is set to I, all others to 0.
- Terminator (3) on both DDLS 170s:
Both switches must be in the same position
0 = inactive
I = active
Fig. Appendix 13: Profibus interface module settings
➜
Activate bus operation
If faults occur during commissioning or if the data transmission path cannot be
activated, see Chapter "Error Diagnosis / Failures and Troubleshooting".
0
I
I 0
Baud rate
93,75k
187,5k
375k
500k
Terminator
Sub-D
to upper
component
1
3
2
These data are only valid for the previous data transmission systems DDLS 170.1
and DDLS 170.2!