background image

1.0 

General 

1.1 

About this document 

These operating instructions are part of the product. They must be 
kept in the vicinity of the product at all times. The careful observance 

of these instructions is the precondition for the proper use and the 
correct  operation  of  the  product.  The  operating  instructions 
correspond to the version of the product and the latest state of the 
underlying safety-related standards. 

1.2 

Safety 

These operating instructions contain essential information that must 
be observed during the installation and operation. For this reason, it 
is imperative that these operating instructions are read by both the 

technician as well as the responsible operator before installation and 
commissioning.  Not  only  must  the  general  safety  instructions  be 
observed that are listed under this main item “Safety”, but also the 
specific safety instructions inserted under the following main points 
with hazard symbols. 

1.3 

Identification of information in the operating 
instructions 

General hazard symbol 

Hazard due to dangerous electrical voltage 

Important information 

2.0 

Warning and safety information for the 
installation and commissioning of the 

control 

2.1 

Fields of application, proper use 

This  switchgear  has  been  designed  for  domestic  and  municipal 
sewage, wastewater and rainwater pump stations. 

Please note the following in regard to the controlling of  
pumps operated in an explosive area: The switchgear itself 

must be installed outside of the explosive area. 

The controls are suitable for wastewater submersible motor pumps 
of the type of protection “d” in zone 1 of the mains. The operating 

manuals of the pumps must be observed. 

When  using  external  4  -  20 mA  level  sensors  and  float  switches 
installed in an explosive area, it will be necessary to use components 
with the requisite certifications.  

It  is essential  for  the switching  of  three-phase current motors  that 
both the setting of the electronic motor current monitoring as well 
as for the settings of mechanical motor protection switches that the 
limit values provided below are adhered to. 

2.2 

Personnel qualifications 

Personnel tasked with the installation, commissioning and 

maintenance of the switchgear must hold the requisite 
qualifications. 

2.3 

Safety instructions for the operator 

Observe the existing regulations governing accident prevention, the 
VDE  specifications  and  stipulations  of  the  local  energy  supply 

company.  When  opening  the  device  (removal  of  the  panel  or 
terminal  cover)  or  working  on  the  pumps,  the  control  must  be 
switched off from the power supply through the fuse or a separate 
main switch. 

Due to safety reasons, the unused cable glands must be sealed with 
blanks or blind caps. 

HAZARD due to dangerous voltage 

When working on the open switchgear,  

there is a risk of death from electric shock.

 

For all work on the open 

device  (removal  of  the  cover  or  terminal  cover)  or  work  on  the 

pumps, the control must always be switched off via the backup fuse 
or  a  separate  main  switch  and  secured against  being  switched  on 
again. This work may only be carried out by a qualified electrician. 

2.3.1 

 

Electrical work

 

HAZARD due to dangerous voltage 

There  is  a  risk  of  death  due  to  electric  shock  in  all  work  on  open 
switchgear. During all work on the open device (removal of the panel 

or the terminal cover) or when working on the pumps, the control 
must be switched off from the power supply through the fuse or a 
separate  main  switch  and  secured  against 

reactivation

.

 

To 

disconnect  the  battery,  pull  out  the  red  +  plug  and  isolate  the 

connection with the yellow cap. This work may only be carried out by 
a qualified electrician. 

Beware of moisture! 

The  device  can  be  damaged  by  penetration  of  moisture.  When 
installing,  pay  attention  to  the  permissible  humidity  and  ensure  a 
flood-proof installation.

 

For the connection, refer to chapter 6.0 "Connection". The technical 
information must be observed.

 

2.4 

Dangers of non-compliance with safety 

information  

The  non-compliance  with  the  safety  information  can  lead  to 
endangerment  for  persons  and  product/system.  Non-compliance 
with  the  safety  information  can  lead  to  the  loss  of  all  rights  for 
damage compensation. 

2.5 

Operating instructions 

When  installing,  commissioning  and  maintaining  the  switchgear 
observe the operating instructions. Always observe the limit values 
cited in the manual. 

A fusing on the mains side of max. 3 x 16 A must be 

performed.

 

Standard version 

5,5 KW  contactors 

Three-phase current  400 V  Max. 12 A 
Alternating current  230 V 

Max. 12 A 

PS

MEGA 

1

www.lesa.de

         

3

 

Содержание PSMEGA 1

Страница 1: ...e pump control Options FS PSMEGA1Freiluftsäule Messglocke V4A Schwimmschalter Tauchsensor Operating Manual www lesa de PSMEGA1_2v0 04092020 LESA Messtechnik Hegholt 59 22179 Hamburg Germany Phone 49 40 641 00 41 Fax 49 40 641 18 36 ...

Страница 2: ...n menu images and notes on configuring the parameters 5 1 Table of possible settings 5 2 Supplements to the individual items in the configuration menu 6 0 Error reports in the display potential errors assistance 6 1 Table of possible fault messages 6 2 The settings in the menu cannot be changed 6 3 Motor contactor monitoring 7 0 Installation pneumatic and electrical connection and connection of 3 ...

Страница 3: ...and maintenance of the switchgear must hold the requisite qualifications 2 3 Safety instructions for the operator Observe the existing regulations governing accident prevention the VDE specifications and stipulations of the local energy supply company When opening the device removal of the panel or terminal cover or working on the pumps the control must be switched off from the power supply throug...

Страница 4: ...rnal audible alarm Collective fault alarm fixed voltage and potential free High water alarm potential free Memory number of pump starts Operating hours counter Ammeter Pump change Forced switchover High interference immunity Easy to operate ATEX mode Service mode Input for float switch dry run protection Analogue outputs 0 10 V and 4 20 mA Fault memory stores the last 4 faults Automatic display il...

Страница 5: ... The green LED will blink If the pump is being run via the manual function then it will automatically shut off after 2 minutes and the green LED will flash irregularly The automatic and manual operation are shut down using this button The green LED is off The pump is switched based on the level The green LED is lit continuously If power is interrupted during manual mode then the control system wil...

Страница 6: ...arm Is deactivated Is activated Is activated The fault information relay will be synchronized Instead of a flashing light it is possible to use a more economic steady burning light Thermal fault 1 Is deactivated Is activated Is deactivated There is no bimetallic contact alarm contact connected to terminal 12 13 Rot field fault Is deactivated Is activated Is activated in case the phase sequence is ...

Страница 7: ... the menu 5 2 8 Error memory Last fault The last 4 errors that occurred remain stored in non volatile memory and can be retrieved in the menu under Last fault Caution Last fault 1 is the last fault that occurred If Last fault 1 is called up in the menu the last errors can be deleted from the memory with the acknowledge button 5 2 9 Rotary field error The rotary field monitoring monitors both the p...

Страница 8: ...y language can also be changed when service mode is deactivated 5 2 17 Menu items data import and export The PSMEGA 1 offers the option of writing and reading configuration files 5 2 18 FatFS Filename At this point the file name is assigned for the configuration and log files The file name PSMEGA 1 is preset A code page can be opened by pressing the select acknowledge button A character can be sel...

Страница 9: ... switch are functioning Reverse signals start stop level The settings for start and stop levels interfere Check level settings Reverse signals start flood level The settings for high water alarm and start level interfere Check settings for level Runtime error Pumps run without interruption for longer than the time set Check function of pump Floating switch malfunction Validation of floating switch...

Страница 10: ...n must be paid that a right rotary field is created The terminals are labelled L1 L2 L3 N The PE terminals are implemented as a brass rail 7 3 1 Connection of the pump The connections L1 L2 L3 of the pump are directly attached to the motor contactor The protective earth conductor is connected to the remaining PE terminal The bimetallic contact which unlocks the pump after it has cooled down needs ...

Страница 11: ...prox 24 volt In the delivered state the measuring range of the level sensor is set in such a manner that it matches the measuring range of the internal pressure sensor In the event that the level sensor should be connected with a different measuring range then the corresponding setting must be changed in the menu see section 5 2 14 The output is active i e the sensor is supplied with voltage by th...

Страница 12: ...e 20 bis 50 C Dimensions 250 x 225 x 115 mm HxWxD Dimensions with cable gland and air connection Fuse 5 x 20 1AT alarm output Voltage supply for 4 20 mA sensor and float switch 24V DC Cable glands 2 x M25 x 1 5 1 x M16 x 1 5 3 x M16 x 1 5 blind plug Hose attachment 6 8 mm Other hose connections are available on request Software version Ver 0 3 When opening the device removal of the panel or termin...

Страница 13: ...12 0 Annex Terminal block wiring diagrams Terminal connection of 3 motors Terminal connection of 1 motors Caution When connecting 1 motors the maximum connected load is 2 4 KW PSMEGA 1 www lesa de 13 ...

Страница 14: ...Relay outputs signal inputs and analogue outputs PSMEGA 1 www lesa de 14 ...

Страница 15: ...A 180 mm B 180mm o 5 0mm PSMEGA 1 www lesa de 15 ...

Страница 16: ...le Alarmmodule GSM Module Messumformer Fernwirk Pumpsysteme Messglocken Pneumatische Leitung Schaltanlagenbau Automatisierung Fernwirktechnik Freiluftsäulen komplett bestückt mit PS1 LCD PS2 LCD Kompaktschaltschrank LCD2 System Metall GfK Außenschränke Leersäulen EVU Anschlusssäule Verschraubungen für pneumatische Leitung Schwimmschalter Tauchsensoren Ultraschallsensoren Stabsonden Druckschalter A...