background image

6.2 

The settings in the menu cannot be changed 

Check in the menu whether the service mode has been activated. 

6.3 

Motor contactor monitoring 

When the contactor is not requested by the control and nevertheless 

a  current  is  measurable  on  one  or  more  phases,  then  the  error 
message “Contactor error” will appear in the display and the audible 
alarm will sound. 

7.0 

Installation, electrical connection 

7.1 

Installation 

The control unit 

PS

MEGA 

is placed in a control box that measures 

250  x  225  x  115

 

mm  (H  x  W  x  D)  with  screw  fittings  and  air 

connection).  There  are  4  drill  holes  on  the  switch  cabinet  for 
mounting, which become visible when the cover is opened. 

7.2 

Hose attachment 

As  standard,  a  hose  screw  connection  8/6 mm  is  delivered  for  the 
hose connection. Optionally, the switching device can be delivered 

with other hose screw connections. The subsequent replacement of 
the  hose  connection  is  also  possible.  The  hose  screw  connection 
must  feature  an  internal  thread  of  G1/8"  towards  the  unit.  During 
replacement, it is important that a 14 mm spanner is used to secure 
the corresponding nut. In any case, the threaded connection must be 
used in combination with a suitable sealant. 

7.3 

Electrical connection power supply and pumps 

The electrical connection must be performed by a qualified 
electrician in accordance with the applicable VDE regulations.

  

HAZARD due to dangerous voltage! 

Improper handling of electrical work may result in a risk of death 
due to electrical voltage! 
A time-lag fusing on the mains side of max. 

3 x 16 A

 must be 

performed. 

Mains connection (3~) PE , L1, L2, L3, N       (image 1a in the 

annex) 

The connecting terminals have been designed for a max. cable cross 

section of 4 mm². Attention must be paid that a right rotary field is 
created. The terminals are labelled L1, L2, L3, N. The PE terminals are 
implemented as a brass rail. 

7.3.1

 

Connection of the pump:

 

The connections L1  L2  L3 of the pump are directly attached to the 
motor contactor. The protective earth conductor is connected to the 
remaining  PE  terminal.  The  bimetallic  contact,  which  unlocks  the 
pump after it has cooled down, needs to be connected to terminal 
12/13; the bimetallic contact that unlocks the pump after pressing 

the “Quittung” button needs to be connected to terminal 13/14 on 
the  upper  circuit  board.  (In  case  Temp.1  is  not  being  connected, 

thermal fault 1

 needs to be deactivated in the menu). 

To operate 1 ~ motors (230V AC) 

a bridge between input 

terminal N an L3 are necessary. 

7.3.2

 

Power supply of the pumps (1~) 

The pump is connected to contactor 

T1 = L

 and 

T3 = N

 

7.3.3

 

Protective winding contacts 

Regulator contact 

Temp 1 / terminal 12/13  

The pump is released automatically after cooling down. 

Limiter contact   

 

Temp 2 / terminal 13/14  

The pump is only released after actuation of the acknowledge push 
button.   

This temperature monitoring must be used for pumps 
located in the 

EX area

When Temp. 1 is not used, then the function must be disabled in 
the menu (see above chapter 5.2.7.).  
When Temp. 2 is not used, then a wire jumper must be used from 

terminal 13 to 14. 

For pumps, in which the bimetallic contact has been switched in such 

a manner that this directly interrupts the current of the pump, the 
message 

“Without load”

 appears, when the bimetallic contact has 

been  triggered.  The  pump  can only  be  taken into  operation  again 
following the acknowledgement. 

The inputs of the controls for the thermal errors are designed for the 
evaluation of the protective winding contacts. Separate evaluation 
devices  must  be  used  for  motors  with  embedded  temperature 

sensors (e.g. PTC resistor) as thermal protection. 

PS

MEGA 

1

www.lesa.de

         

10

 

Содержание PSMEGA 1

Страница 1: ...e pump control Options FS PSMEGA1Freiluftsäule Messglocke V4A Schwimmschalter Tauchsensor Operating Manual www lesa de PSMEGA1_2v0 04092020 LESA Messtechnik Hegholt 59 22179 Hamburg Germany Phone 49 40 641 00 41 Fax 49 40 641 18 36 ...

Страница 2: ...n menu images and notes on configuring the parameters 5 1 Table of possible settings 5 2 Supplements to the individual items in the configuration menu 6 0 Error reports in the display potential errors assistance 6 1 Table of possible fault messages 6 2 The settings in the menu cannot be changed 6 3 Motor contactor monitoring 7 0 Installation pneumatic and electrical connection and connection of 3 ...

Страница 3: ...and maintenance of the switchgear must hold the requisite qualifications 2 3 Safety instructions for the operator Observe the existing regulations governing accident prevention the VDE specifications and stipulations of the local energy supply company When opening the device removal of the panel or terminal cover or working on the pumps the control must be switched off from the power supply throug...

Страница 4: ...rnal audible alarm Collective fault alarm fixed voltage and potential free High water alarm potential free Memory number of pump starts Operating hours counter Ammeter Pump change Forced switchover High interference immunity Easy to operate ATEX mode Service mode Input for float switch dry run protection Analogue outputs 0 10 V and 4 20 mA Fault memory stores the last 4 faults Automatic display il...

Страница 5: ... The green LED will blink If the pump is being run via the manual function then it will automatically shut off after 2 minutes and the green LED will flash irregularly The automatic and manual operation are shut down using this button The green LED is off The pump is switched based on the level The green LED is lit continuously If power is interrupted during manual mode then the control system wil...

Страница 6: ...arm Is deactivated Is activated Is activated The fault information relay will be synchronized Instead of a flashing light it is possible to use a more economic steady burning light Thermal fault 1 Is deactivated Is activated Is deactivated There is no bimetallic contact alarm contact connected to terminal 12 13 Rot field fault Is deactivated Is activated Is activated in case the phase sequence is ...

Страница 7: ... the menu 5 2 8 Error memory Last fault The last 4 errors that occurred remain stored in non volatile memory and can be retrieved in the menu under Last fault Caution Last fault 1 is the last fault that occurred If Last fault 1 is called up in the menu the last errors can be deleted from the memory with the acknowledge button 5 2 9 Rotary field error The rotary field monitoring monitors both the p...

Страница 8: ...y language can also be changed when service mode is deactivated 5 2 17 Menu items data import and export The PSMEGA 1 offers the option of writing and reading configuration files 5 2 18 FatFS Filename At this point the file name is assigned for the configuration and log files The file name PSMEGA 1 is preset A code page can be opened by pressing the select acknowledge button A character can be sel...

Страница 9: ... switch are functioning Reverse signals start stop level The settings for start and stop levels interfere Check level settings Reverse signals start flood level The settings for high water alarm and start level interfere Check settings for level Runtime error Pumps run without interruption for longer than the time set Check function of pump Floating switch malfunction Validation of floating switch...

Страница 10: ...n must be paid that a right rotary field is created The terminals are labelled L1 L2 L3 N The PE terminals are implemented as a brass rail 7 3 1 Connection of the pump The connections L1 L2 L3 of the pump are directly attached to the motor contactor The protective earth conductor is connected to the remaining PE terminal The bimetallic contact which unlocks the pump after it has cooled down needs ...

Страница 11: ...prox 24 volt In the delivered state the measuring range of the level sensor is set in such a manner that it matches the measuring range of the internal pressure sensor In the event that the level sensor should be connected with a different measuring range then the corresponding setting must be changed in the menu see section 5 2 14 The output is active i e the sensor is supplied with voltage by th...

Страница 12: ...e 20 bis 50 C Dimensions 250 x 225 x 115 mm HxWxD Dimensions with cable gland and air connection Fuse 5 x 20 1AT alarm output Voltage supply for 4 20 mA sensor and float switch 24V DC Cable glands 2 x M25 x 1 5 1 x M16 x 1 5 3 x M16 x 1 5 blind plug Hose attachment 6 8 mm Other hose connections are available on request Software version Ver 0 3 When opening the device removal of the panel or termin...

Страница 13: ...12 0 Annex Terminal block wiring diagrams Terminal connection of 3 motors Terminal connection of 1 motors Caution When connecting 1 motors the maximum connected load is 2 4 KW PSMEGA 1 www lesa de 13 ...

Страница 14: ...Relay outputs signal inputs and analogue outputs PSMEGA 1 www lesa de 14 ...

Страница 15: ...A 180 mm B 180mm o 5 0mm PSMEGA 1 www lesa de 15 ...

Страница 16: ...le Alarmmodule GSM Module Messumformer Fernwirk Pumpsysteme Messglocken Pneumatische Leitung Schaltanlagenbau Automatisierung Fernwirktechnik Freiluftsäulen komplett bestückt mit PS1 LCD PS2 LCD Kompaktschaltschrank LCD2 System Metall GfK Außenschränke Leersäulen EVU Anschlusssäule Verschraubungen für pneumatische Leitung Schwimmschalter Tauchsensoren Ultraschallsensoren Stabsonden Druckschalter A...

Отзывы: