Pushbutton switch – Manual operation 

Pushbutton switch – Off 

Pushbutton switch – Automatic operation 

Pushbutton switch – Selection / acknowledgement 

Rotary knob – Display

 

4.1

.

Display 

All  information  and  settings  can  be  queried  using  the  digital 
potentiometer

 

display

. If a setting is to be changed, the regulator is 

adjusted  until  the  corresponding  setting  appears  on  the  display.  
Now press the 

select / cancel

 button. The value last saved will start to 

blink. The digital potentiometer 

display

 can now be used to change 

the setting. Quick turns will change the values more rapidly, while 
slow turns make it possible to make more precise changes. Once the 
desired  value  has  been  reached,  use  the 

select  /  cancel

  button  to 

confirm. The value will stop blinking and be stored. Check all values 
prior to commissioning. The display will automatically return to the 
default setting after 20 seconds. 

The operating hours and pump starts are counted 
continuously, it is not possible to adjust or reset them.  

4.2 

Operating elements 

Pressing the digital potentiometer will query all settings as  
well as error messages, operating hours, number of pump 
starts  and  motor  current.  Moreover,  the  settings  are 

performed using the digital potentiometer. If the knob is not moved 
for  more  than  20 seconds,  then  the  display  will  jump  back  to  the 

default setting. (see above, Configuration chapter) 

Pressing this button will confirm the errors overcurrent,  
pump without load and thermal error 2 after removal of  
the cause. In the event that an error should continue to be 

present,  then  only  the  common  error  report  relay  and  the  piezo 
buzzer will be shut off. This also applies to all other errors and the 
high water alarm. Settings can still be changed using the button.  

Pressing this button will manually put the pump into  
operation. The green LED will blink. If the pump is being  

run via the manual function, then it will automatically shut off after 
2 minutes and the green LED will flash irregularly. 

The automatic and manual operation are shut down using  
this button. The green LED is off. 

The pump is switched based on the level. The green LED is 
lit continuously. 

 If  power  is  interrupted  during  manual  mode,  then  the 
control  system  will  return  to  the  automatic  mode.  The 
operation modes “Auto” and “0” are stored in non-volatile 
memory. 

4.3 

Function display via light-emitting diodes 

LED - red  

= Fault, high water alarm 

LED - solid yellow      

= The pump is in operation 

LED - flashing yellow 

= The pump is in operation  
     via the overrun function 

LED - solid green                      = Automatic mode 
LED - flashing green                  = Manual mode 

LED - irregular green flashing = Manual mode   

  has shut off after 2 min 

LED - blue:                     (Function only with module) 

Continuous flashing= 

The board is in the initialization  

  Phase 

Continuous light   = 

The board is initialized and has  

     

 connected to the provider 

Single Flash, 

Long break 

  = 

The modem does not answer 

Double Flash, 

Long break 

  = 

The SIM card cannot be found

 

Triple Flash 

  = 

The GSM signal strength is too weak 

4.4 

Display

 

In the upper area of the display, there is a bar graph for the level (L) 
and two bar graphs for the current of the pumps (I). In the display’s 
basic  setting,  the  level  and  the  operating  hours  are  additionally 

displayed in numbers below the bar graph displays. If the pump is in 
operation,  the  motor  current  will  be  displayed.  If  any  disruptions 
occur,  then  they  will  be  displayed  alternatingly  on  the  display’s 
bottom line. 

4.4.1

 

Automatic deactivation of the background 
lighting:

 

If no further settings are performed on the device, the background 
lighting switches off automatically after 30 seconds. As soon as the 
rotary  switch  or  one  of  the  pushbutton  switches  is  actuated,  the 
background lighting switches on again. This function can be disabled 
via the menu and then the background lighting remains switched on. 

PS

MEGA 

1

www.lesa.de

         

5

 

Содержание PSMEGA 1

Страница 1: ...e pump control Options FS PSMEGA1Freiluftsäule Messglocke V4A Schwimmschalter Tauchsensor Operating Manual www lesa de PSMEGA1_2v0 04092020 LESA Messtechnik Hegholt 59 22179 Hamburg Germany Phone 49 40 641 00 41 Fax 49 40 641 18 36 ...

Страница 2: ...n menu images and notes on configuring the parameters 5 1 Table of possible settings 5 2 Supplements to the individual items in the configuration menu 6 0 Error reports in the display potential errors assistance 6 1 Table of possible fault messages 6 2 The settings in the menu cannot be changed 6 3 Motor contactor monitoring 7 0 Installation pneumatic and electrical connection and connection of 3 ...

Страница 3: ...and maintenance of the switchgear must hold the requisite qualifications 2 3 Safety instructions for the operator Observe the existing regulations governing accident prevention the VDE specifications and stipulations of the local energy supply company When opening the device removal of the panel or terminal cover or working on the pumps the control must be switched off from the power supply throug...

Страница 4: ...rnal audible alarm Collective fault alarm fixed voltage and potential free High water alarm potential free Memory number of pump starts Operating hours counter Ammeter Pump change Forced switchover High interference immunity Easy to operate ATEX mode Service mode Input for float switch dry run protection Analogue outputs 0 10 V and 4 20 mA Fault memory stores the last 4 faults Automatic display il...

Страница 5: ... The green LED will blink If the pump is being run via the manual function then it will automatically shut off after 2 minutes and the green LED will flash irregularly The automatic and manual operation are shut down using this button The green LED is off The pump is switched based on the level The green LED is lit continuously If power is interrupted during manual mode then the control system wil...

Страница 6: ...arm Is deactivated Is activated Is activated The fault information relay will be synchronized Instead of a flashing light it is possible to use a more economic steady burning light Thermal fault 1 Is deactivated Is activated Is deactivated There is no bimetallic contact alarm contact connected to terminal 12 13 Rot field fault Is deactivated Is activated Is activated in case the phase sequence is ...

Страница 7: ... the menu 5 2 8 Error memory Last fault The last 4 errors that occurred remain stored in non volatile memory and can be retrieved in the menu under Last fault Caution Last fault 1 is the last fault that occurred If Last fault 1 is called up in the menu the last errors can be deleted from the memory with the acknowledge button 5 2 9 Rotary field error The rotary field monitoring monitors both the p...

Страница 8: ...y language can also be changed when service mode is deactivated 5 2 17 Menu items data import and export The PSMEGA 1 offers the option of writing and reading configuration files 5 2 18 FatFS Filename At this point the file name is assigned for the configuration and log files The file name PSMEGA 1 is preset A code page can be opened by pressing the select acknowledge button A character can be sel...

Страница 9: ... switch are functioning Reverse signals start stop level The settings for start and stop levels interfere Check level settings Reverse signals start flood level The settings for high water alarm and start level interfere Check settings for level Runtime error Pumps run without interruption for longer than the time set Check function of pump Floating switch malfunction Validation of floating switch...

Страница 10: ...n must be paid that a right rotary field is created The terminals are labelled L1 L2 L3 N The PE terminals are implemented as a brass rail 7 3 1 Connection of the pump The connections L1 L2 L3 of the pump are directly attached to the motor contactor The protective earth conductor is connected to the remaining PE terminal The bimetallic contact which unlocks the pump after it has cooled down needs ...

Страница 11: ...prox 24 volt In the delivered state the measuring range of the level sensor is set in such a manner that it matches the measuring range of the internal pressure sensor In the event that the level sensor should be connected with a different measuring range then the corresponding setting must be changed in the menu see section 5 2 14 The output is active i e the sensor is supplied with voltage by th...

Страница 12: ...e 20 bis 50 C Dimensions 250 x 225 x 115 mm HxWxD Dimensions with cable gland and air connection Fuse 5 x 20 1AT alarm output Voltage supply for 4 20 mA sensor and float switch 24V DC Cable glands 2 x M25 x 1 5 1 x M16 x 1 5 3 x M16 x 1 5 blind plug Hose attachment 6 8 mm Other hose connections are available on request Software version Ver 0 3 When opening the device removal of the panel or termin...

Страница 13: ...12 0 Annex Terminal block wiring diagrams Terminal connection of 3 motors Terminal connection of 1 motors Caution When connecting 1 motors the maximum connected load is 2 4 KW PSMEGA 1 www lesa de 13 ...

Страница 14: ...Relay outputs signal inputs and analogue outputs PSMEGA 1 www lesa de 14 ...

Страница 15: ...A 180 mm B 180mm o 5 0mm PSMEGA 1 www lesa de 15 ...

Страница 16: ...le Alarmmodule GSM Module Messumformer Fernwirk Pumpsysteme Messglocken Pneumatische Leitung Schaltanlagenbau Automatisierung Fernwirktechnik Freiluftsäulen komplett bestückt mit PS1 LCD PS2 LCD Kompaktschaltschrank LCD2 System Metall GfK Außenschränke Leersäulen EVU Anschlusssäule Verschraubungen für pneumatische Leitung Schwimmschalter Tauchsensoren Ultraschallsensoren Stabsonden Druckschalter A...

Отзывы: