52
MENU 6: PROGRAMMABLE LOGIC AND TIMERS
LEROY-SOMER
6.09
:Catch a spinning motor
Adjustment range : 0 to 3
Factory setting
: 0
If this parameter is enabled (
6
6
.
.
0
0
9
9
= 1 to 3), when there is a
run command or after a mains supply break, the drive
executes a procedure to calculate the motor frequency and
direction of rotation. It will automatically recalibrate the output
frequency to the measured value and reaccelerate the motor
up to the reference frequency.
• If the load is stationary at the time of the run
command or when the mains supply returns, this
operation may cause the machine to rotate in both
directions before the motor accelerates.
• Before enabling this function, check that there is
no danger to equipment and personnel.
6.10
:Enable reduced-voltage operation
0 (OFF):
The DC bus undervoltage detection thresholds are
unchanged.
1 (On):
Used to modify the DC bus undervoltage detection
thresholds in 400V (T) drives, in order to be at the same levels
as 230V drives. This enables a 400V (T) rated motor to be
supplied with 230V when necessary, without the drive
passing into the trip state.
Note:
This parameter is not active for "TL" ratings (
6
6
.
.
1
1
0
0
is
fixed at 1).
6.11
:Enable forward key
Adjustment range: 0 or 1
Factory setting
: CP version = 1
SET version = 0
0 (OFF):
Local control FWD key disabled.
1 (On): Local control FWD key enabled.
6.12
:Enable stop key
Adjustment range : 0 or 1
Factory setting
: 1
0 (OFF):
Local control Stop key disabled.
1 (On): Local control Stop key enabled.
If the Stop key is enabled, it is taken into account even if
control is via the terminals.
If a stop is ordered via the local console while a run command
is present, the run command on the terminals must be
opened to authorise restarting.
6.13
:Enable reverse key
Adjustment range : 0 or 1
Factory setting
: 0
0 (OFF): Local control REV key disabled.
1 (On):
Enables the local control REV key.
6.14
:Not used
6.15
:Drive enable
Adjustment range : 0 or 1
Factory setting
: 1
0 (diSb): Drive disabled.
1 (Enab):
Drive enabled.
CAUTION:
Disabling via the drive terminals overrides 6
6
.
.
1
1
5
5
(see
8
8
.
.
1
1
0
0
). If the drive is disabled via the terminals, the user
can then disable or enable the drive via 6
6
.
.
1
1
5
5
.
6.16
:Not used
6.17
:Reset energy meter
Adjustment range : 0 or 1
Factory setting
: 0
When this parameter is at 1, the counters
6
6
.
.
2
2
4
4
and
6
6
.
.
2
2
5
5
are
reset to 0.
6.18, 6.19
and
:Not used
6.20
:Powered-up time: years.days
Adjustment range : 0 to 9.364 years, days
This parameter records for how many years and days the
drive has been powered up.
6.21
:Powered-up time: hours.minutes
Adjustment range : 0 to 23.59 hrs, min
This parameter records for how many hours and minutes the
drive has been powered up.
After 23.59,
6
6
.
.
2
2
1
1
returns to 0 and
6
6
.
.
2
2
0
0
is incremented by
one day.
6.22
:Run time: years.days
Adjustment range : 0 to 9.364 (years, days)
This parameter records the number of years and days of
operation since the drive was first powered up.
6.23
:Run time: hours.minutes
Adjustment range : 0 to 23.59 (hrs, min)
This parameter records the number of hours and minutes of
operation since the drive was first powered up.
After 23.59,
6
6
.
.
2
2
3
3
returns to 0 and
6
6
.
.
2
2
2
2
is incremented by 1
day.
6
6
.
.
0
0
9
9
Functions
0 (no)
Catch a spinning motor function disabled
1 (On.2d)
Enable to catch a spinning motor which is
rotating clockwise or anti-clockwise
2 (On.Fd)
Enable to catch a spinning motor which is
rotating clockwise only
3 (On.rS)
Enable to catch a spinning motor which is
rotating anti-clockwise only
6
6
.
.
0
0
9
9
6
6
.
.
1
1
0
0
6
6
.
.
1
1
1
1
6
6
.
.
1
1
2
2
6
6
.
.
1
1
3
3
6
6
.
.
1
1
4
4
6
6
.
.
1
1
5
5
6
6
.
.
1
1
6
6
6
6
.
.
1
1
7
7
6
6
.
.
1
1
8
8
6
6
.
.
1
1
9
9
6
6
.
.
2
2
0
0
6
6
.
.
2
2
1
1
6
6
.
.
2
2
2
2
6
6
.
.
2
2
3
3
Содержание PROXIDRIVE
Страница 8: ...8 ADVANCED USER GUIDE PROXIDRIVE IP66 variable speed drive LEROY SOMER 3756 en 05 2004 b Notes ...
Страница 24: ...24 ADVANCED USER GUIDE PROXIDRIVE IP66 variable speed drive MENU 2 RAMPS LEROY SOMER 3756 en 05 2004 b Notes ...
Страница 104: ...104 ADVANCED USER GUIDE PROXIDRIVE IP66 variable speed drive MENU 15 RESERVED LEROY SOMER 3756 en 05 2004 b Notes ...
Страница 121: ...121 ADVANCED USER GUIDE PROXIDRIVE IP66 variable speed drive OPERATION WITH MODBUS RTU LEROY SOMER 3756 en 05 2004 b ...
Страница 122: ...122 ADVANCED USER GUIDE PROXIDRIVE IP66 variable speed drive OPERATION WITH MODBUS RTU LEROY SOMER 3756 en 05 2004 b ...
Страница 123: ......
Страница 124: ......