: Preset speeds/inching (jog)
Adjustment range : 0 or 1.
Factory setting
: 0.
Mnemonic :
C1-8.
b20 = 0 : preset speeds 1 to 3 can be selected via a
combination of terminals B8, B9, as can the
inching operation function via terminal B10.
b20 = 1 : preset speeds 1 to 7 can be selected via a
combination of terminals B8, B9, B10.
Note : the inching function is enabled when b20 = 0 and
terminal B10 is linked to 0V, with the direction of rotation
selected by terminals C10 or C12. The motor rotates at
the speed set via P27 until the link to 0V of one of
terminals B10, C10 or C12 is opened.
Note :
- 0 = terminal not connected to B7 (0V),
1 = terminal connected to B7 (0V).
- Terminals B10, B9 and B8 are not active if the
inverter is in " slave " mode (terminal C11 at 0V and
b6 = 1, see b6).
- To obtain a negative speed, press the (FWD/REV)
button on the operator panel during programming
: Not used
Adjustment range : 0 or 1.
Factory setting
: 0.
Mnemonic :
C1-7.
: Standard or specific ramps
Adjustment range : 0 or 1.
Factory setting
: 0.
Mnemonic :
C1-9 and C1-6.
The combination of b21 and b23 is used to select
specific ramps for preset speeds or to program specific
ramps for the frequency reference (using terminals B8,
B9 and B10).
: Information on terminals B1 and B2
Adjustment range : 0 or 1.
Factory setting
: b24 = b25 = 0.
Mnemonic :
C1-4 and C1-5.
The combination of b24 and b25 determines
the output signals available at terminals B1 and B2.
Note : In each case it indicates the output frequency of
the inverter.
42
Frequency inverters
FMV 2107
FMV 2307
Terminals
Associated
b20
B10 B9 B8
Function available
parameter
0 or 1
0
0
0 Frequency reference
-
0 or 1
0
0
1 Preset speed 1
P20
0 or 1
0
1
0 Preset speed 2
P21
0 or 1
0
1
1 Preset speed 3
P22
0
1
0
0 Inching operation
P27
1
1
0
0 Preset speed 4
P23
1
1
0
1 Preset speed 5
P24
1
1
1
0 Preset speed 6
P25
1
1
1
1 Preset speed 7
P26
1
0
0
0 Frequency reference
-
b
b
2
2
0
0
b
b
2
2
2
2
b
b
2
2
1
1
-
-
b
b
2
2
3
3
b21 b23
0
0
The preset speeds use P02 and P03.
1
0
The preset speeds use P30 to
P36 and P40 to P46.
1
1
The preset speeds use P30 to
P36 and P40 to P46.
0
1
The analogue frequency reference uses
specific ramps as follows :
B10
B9
B8
Ramps used
0
0
0
P02 and P03
0
0
1
P30 and P40
0
1
0
P31 and P41
0
1
1
P32 and P42
1
0
0
P33 and P43
1
0
1
P34 and P44
1
1
0
P35 and P45
1
1
1
P36 and P46
If b20 = 1 : all ramps in the table
are available.
If b20 = 0 : only the first 4 lines
are available and terminal B10
is released enabling
JOG operation.
b
b
2
2
4
4
-
-
b
b
2
2
5
5
b24 b25
Signals
Terminal B1
Terminal B2
0
0
Analogue voltage signal
0 to
±
10VDC
indication of frequency
0V = 0 Hz
+10V = P1 (FWD)
- 10V = P1 (REV)
Analogue current signal
4 to 20mA
indication of load
20mA corresponding
to 150 % motor or
generator load.
0
1
Analogue voltage signal
0 to
±
10VDC
indication of load
+10V = 150 % motor
load
- 10V = 150 %
generator load
Analogue current signal
4 to 20mA
indication of frequency
4mA = 0Hz
20mA = P1
1
0
Logic voltage signal
0 or 10V
- 0V = P5 not reached
10V = P5 reached
Analogue current signal
4 to 20mA
indication of load
20mA corresponding
to 150 % motor or
generator load.
1
1
Logic voltage signal
0 or 10V
- 0V = P5 not reached
10V = P5 reached
Analogue current signal
4 to 20mA
indication of frequency
4mA = 0Hz
20mA = P1