1.4 - Environmental characteristics
1.4.1 - General
b - Installation in a non-ventilated cubicle
The minimum required surface area for heat
exchange is calculated from the following equation :
where :
Pj = loss from all heat-producing equipment (W).
Tj = maximum permissible ambient operating
temperature (
°
C).
Tamb = maximum ambient external temperature (
°
C).
k = thermal transmission cœfficient.
S = heat exchange area (m
2
).
k = 5.5 for 2mm thick sheet steel.
Example : installation of an FMV in a non-ventilated IP 54
cubicle (cubicle placed against a wall).
Pj = 114W (FMV 2107 2,5M) for switching F = 11.7kHz.
Tj = 40
°
C.
Tamb = 30
°
C for example.
k = 5.5.
The calculated heat exchange area is S = 2.07m
2
and
S = 2 (AB) + AC + BC.
Taking the following values for A and B :
A = 1.8 m (height) - B = 0.6 m (depth),
the minimum calculation for C = 0.39 m.
c - Installation in a ventilated cubicle
If it is possible to use forced ventilation (FV) the size of
the cubicle can be reduced. A minimum space of 100 mm
should be left around the inverter.
The flow rate of FV in m
3
/h is calculated using the
formula
for the previous example.
11
Frequency inverters
FMV 2107
FMV 2307
Characteristics
Level
Ingress protection
IP31
Storage temperature
- 40
°
C to + 50
°
C, 12 months maximum.
Operating temperature
- 10
°
C to + 50
°
C.
Altitude
•
≤
1000 m without derating.
• Derating : 1 % of I
N
per 100 m above 1000m up to 4000 maximum.
Humidity
Non condensing.
Vibration
According to IEC 68-2-34 (0.01g
2
/Hz acceleration)
Shocks
According to IEC 68-2-27 (50g peak acceleration)
Immunity
According to : - IEC 801-2 Level 3
- IEC 801-3 Level 3
- IEC 801-4 Level 3
Emissions
conducted According to : - EN 50081-1 (VDE 875 N) with : 2.9 kHz switching frequency
and supply filter
- EN 50081-2 (VDE 875 G) with supply filter
radiated According to EN 50081-2
1.4.2 - Installation in a cubicle
Installing the inverter in a cubicle calls for special precautions with regard to the size of the enclosure. It is important to check
that there is sufficient heat dissipation.
a - Table of losses in Watts (W)
- Table of flow rates for forced ventilation (m
3
min)
Switching
FMV 2107
FMV 2307
FMV 2307
frequency
1.5M
2.5M
3.5M
1.5TL
2.5TL
3.5TL
1.5T
2T
2.5T
3.5T
4.5T
5.5T
2.9 kHz
64
67
82
52
62
81
41
46
55
75
90
110
5.9 kHz
70
73
115
61
72
93
44
57
67
89
105
120
8.8 kHz
88
93
131
67
80
108
49
65
73
97
120
135
11.7 kHz
90
114
140
71
85
124
61
72
89
119
138
148
S =
Pj
k (Tj - Tamb)
Forced
FMV 2107
FMV 2307
FMV 2307
ventilation
1.5M
2.5M
3.5M
1.5TL
2.5TL
3.5TL
1.5T
2T
2.5T
3.5T
4.5T
5.5T
Flow rate (m
3
min)
-
0,72
0,72
-
0,72
0,72
-
-
0,72
0,72
0,72
0,72
A
C
B
V =
3.1 Pj
Tj - Tamb
= 35,3 m
3
/h