20
Before
a
disinfection
cycle
is
initiated,
the
MIN
and
MAX
settings
MUST
be
changed
to
accommodate
higher
outlet
temperatures.
MIN
setting
should
be
set
to
the
minimum
desired
disinfection
temperature.
MAX
setting
should
be
changed
to
the
maximum
desired
disinfection
temperature.
After
the
first
minute
of
disinfection,
an
error
will
be
triggered
if
the
outlet
temperature
is
below
the
MIN
or
above
the
MAX
settings,
which
will
automatically
end
the
cycle.
SEVERE
BURNS,
SEVERE
INJURY
AND/OR
EVEN
DEATH
MAY
OCCUR
IF
SUCH
PROVISIONS
ARE
NOT
IN
PLACE
WHEN
SELECTING
‘Y’
ON
THIS
MENU!
Once
‘
Y
’
(yes)
is
chosen,
the
authorized
user
will
then
be
prompted
to
enter
the
desired
disinfection
time,
adjustable
in
15
minute
increments,
up
to
12
hours.
Choose
the
desired
time
and
press
ENTER
to
start
the
timer.
Extreme
care
must
be
taken
during
the
disinfection
process!
Disinfection
can
be
cancelled
at
anytime
by
pressing
the
ENTER
Key.