Pressing
▼
4
times
displays
Err
TTML
This
indicates
the
TIME
TO
MAKE
LIVE,
which
is
an
elapsed
time
in
seconds
as
to
when
an
actual
error
will
be
identified
by
the
processor
(e.g.
low
inlet
supply
pressure)
and
then
subsequently
recognized
as
a
true
error
and
displayed
on
the
LCD
screen.
The
error
must
exist
for
at
least
this
minimum
time
before
being
considered
a
true
error.
The
default
value
is
15
seconds.
Commissioning
Menu
Screen
6:
Error
Time
to
Live
Pressing
▼
5 times
displays
Err
TTL
This
indicates
TIME
TO
LIVE,
which
is
a
time
in
seconds
and
starts
as
soon
as
Err TTML
has
elapsed.
An
error
that
exists
past
both
TTML
and
TTL
will
require
user
recognition
to
clear
error
from
screen
by
pressing
ENTER
.
If
the
problem
corrects
itself
during
the
elapsing
TTL
time,
the
Error
will
be
automatically
removed
from
the
display
on
the
user
interface
and
therefore
does
not
exist
in
memory.
Default
time
is
60
seconds.
Commissioning
Menu
Screen
7:
Auxiliary
Flow
Sensor
#2
Pressing
▼
6
times
displays
Aux2
flow:
N
or
Y
This
indicates
whether
or
not
the
configurable
auxiliary
channel,
if
utilized,
is
a
2
nd
flow
meter
or
a
3
rd
pressure
sensor
supplied
with
the
Nucleus
unit.
Select
‘
Y
’
if
a
flow
meter
is
used
or
‘
N
’
if
a
pressure
sensor
is
used.
See
Page
28
for
proper
wiring
configuration
15
Commissioning Menu Screen 5:
Error Time to Make Live