Commissioning Menu Screen 16:
Maximum Alarm Temperature for Temperature Sensor #8
Pressing
▼
15
times
displays
Commissioning
Temp
8
max:
185F
This
is
the
maximum
temperature
for
RTD
probe
T8.
Any
temperature
above
this
setting
at
T8
will
trigger
an
error
message.
Default
setting
is
185
˚
F
19
‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐
THERMAL
DISINFECTION
WARNING: The
Nucleus
Digitally
Controlled
Mixing
Valve
is
equipped
with
the
ability
to
program
the
valve
to
move
to
full
hot
position,
which
will
allow
ONLY
high
temperature
hot
supply
water
to
enter
the
device
and
subsequently
deliver
that
high
temperature
water
downstream
of
the
device.
There
is
inherent
risk
in
this
procedure
and
it
is
a
feature
which
allows
the
user
to
‘Disinfect’
the
plumbing
system
downstream
of
the
device.
Commissioning
Menu
Screen
17:
Thermal
Disinfection
Pressing
▼
16
times
displays
Commissioning
Disinfect:
N
or
Y
BEFORE THIS MODE IS ENGAGED, AN AUTHORIZED USER MUST BE AWARE OF THE POTENTIAL RISKS
TO END USERS DOWNSTREAM OF THIS DEVICE, AND MUST ALSO MAKE PROVISIONS TO PUT SAFETY
MEASURES IN PLACE DURING THE DISINFECTION STAGE TO ENSURE USER SAFETY.
SEVERE
BURNS,
SEVERE
INJURY
AND/OR
EVEN
DEATH
MAY
OCCUR
IF
SUCH
PROVISIONS
ARE
NOT
IN
PLACE
WHEN
SELECTING
‘Y’
ON
THIS
MENU!