Commissioning
6.3
Settings and displays in the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3
Settings and displays in the »Engineer«
Setting / display
Description
General
General information on the node type or the synchronisation of the
application
EPL address (project)
Setting of the POWERLINK address (node ID:
/
)
You can set the address ’1’ ... ’100’ for the communication module.
Current EPL device address
Display of the current POWERLINK device address (
EPL host name
The DNS-compatible
host name
/
) has to be non-
ambiguous within the network domain.
The device name ...
• consists of max. 15 characters ([A ... Z], [a ... z], [0 ... 9], [ - ]);
• starts with a letter;
• ends with a letter or a digit.
EPL IP address
The IP address (
) is created from the POWERLINK address
(Node ID): 192.168.100.[
/
Example: 192.168.100.1 = 0xC0.A8.64.01
EPL MAC address
Display of the MAC address (
Open/close advanced
settings
Here, the POWERLINK communication can be reset.