10
Parameter reference
10.3
Parameters of the communication module for slot MXI2
94
Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14045
C14060
Parameter | Name:
C14045 | EPL host name
Data type: VISIBLE_STRING
Index: 10530 = 0x2922
EPL index: 0x1F9A
The code defines a DNS-compatible device name. The length is limited to 15 characters.
The device name must be unambiguous within the network domain.
Naming convention:
The device name
• starts with a character
• ends with a character or digit
The device name consists of
• letters ([A ... Z], [a ... z])
• digits ([0 ... 9])
• hyphen ([ - ])
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C14060 | EPL cycle time
Data type: UNSIGNED_32
Index: 10515 = 0x2913
EPL index: 0x1006
The code declares the length of the EPL cycle in
s.
• In the configured state, this code must have an identical value in all EPL nodes.
• The selected value must correspond to the actual bus cycle time so that the internal monitoring functions work
correctly.
Selection list
(Lenze setting printed in bold)
500 0.5
1000 1
2000 2
3000 3
4000 4
5000 5
6000 6
7000 7
8000 8
9000 9
10000 10
11000 11
12000 12
13000 13
14000 14
15000 15
16000 16
17000 17
18000 18
19000 19
20000 20
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT