Parameters of the communication module for slot MXI2
90
Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14029
Description of the bits 0 ... 31
*) Not permissible for 9400 Servo Drives.
Parameter | Name:
C14029 | EPL node declaration MN
Data type: UNSIGNED_32
Index: 10546 = 0x2932
EPL index: See subcodes
The code describes managing node, diagnostic device, and EPL router as well as their properties.
Value is bit-coded:
Bit 0 ... 31 see below
Subcodes
Lenze setting
Info
EPL index
C14029/1
2147483661
(0x8000000D)
EPL node assignment managing
node
0x1F81.0xF0
C14029/2
0
EPL node assignment diagnostic
device
0x1F81.0xFD
C14029/3
2147483655
(0x80000007)
EPL node assignment router
0x1F81.0xFE
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Bit
Relevance
Lenze
Value
Description
MN
CN
0 (LSB)
0, 1
0
EPL node with this ID does not exist.
1
EPL node with this ID exists.
1
0, 1
0
EPL node with this ID is not a controlled node.
1
EPL node with this ID is a controlled node.
2
1
0
*)
On detection of a booting controlled node, the application will not be informed.
1
On detection of a booting controlled node, the application will be informed and the controlled node
will be started.
3
1
0
Optional controlled node
1
Obligatory controlled node
4
0
0
The managing node is allowed to send reset commands.
1
*)
The managing node must not send any reset command.
5
0
0
Software version verification of the controlled node is not required.
1
*)
Software version verification of the controlled node is required.
6
0, 1
0
Automatic application software update is not allowed.
1
Automatic application software update is allowed.
7
-
-
0
0
Reserved / No function
8
0, 1
0
Isochronously accessed controlled node
1
Asynchronously accessed controlled node (bit 9 is irrelevant)
9
0
0
Continuously accessed controlled node
1
Multiplex EPL nodes are supported.
10
0
0
No "POWERLINK to standard Ethernet" router function.
1
The device can be used as an "POWERLINK to standard Ethernet" router (router type 1).
11
0
0
No "POWERLINK to fieldbus" router function.
1
The device can be used as an "POWERLINK to fieldbus" router (router type 1).
12
0
0
The managing node does not send any PRes frames
1
The managing node sends PRes frames
13 ... 30
-
-
0
0
Reserved / No function
31
(MSB)
0, 1
0
Bits 0 ... 30 inhibited
1
Bits 0 ... 30 enabled