Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
51
8
Diagnostics
8.2
Troubleshooting with module signalling
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[8-3]
Diagnostics - POWERLINK operation
E94YCEP053
3. Diagnostics - EPL operation
Make further error
search with the
Engineer.
Go back to point 3.
Standard device: Make a
fault reset.
Then wait 30 s.
EPL master:
ME on?
Make a fault reset
at the standard
Device.
End
Wait 30 s.
EPL master: BS
on / blinking?
yes
no
yes
on
blinking / off
no
End
on
Make further error
search with the
Engineer.
Wait 30 s.
EPL master: BS
on / blinking?
EPL master:
ME on?
BE on?
blinking / off
Note!
The LEDs
ME
(Module Error),
BE
(Bus Error) and
BS
(Bus Status) refer to the Lenze
communication module E94AYCEP as Managing Node.
This status display applies analogously to the managing nodes of other manufacturers.