To install the full-length-adapter bracket, complete the following steps:
1. Orient the riser-card assembly as shown.
2. Remove the full-length-adapter bracket from the storage location.
a. Press the bracket tab
3
and slide the bracket toward the end of the
riser-card assembly.
b. Push the bracket out of the storage location on the riser-card assembly.
3. Align the bracket with the end of the riser-card assembly as shown.
4. Place the two hooks
1
in the two openings
2
in the end of the riser-card
assembly.
5. Press the bracket tab
3
and slide the bracket to the right until it clicks into
place.
6. Return to the adapter-installation instructions.
Storing the full-length-adapter bracket
If you are removing a full-length adapter in the upper riser-card PCI slot and will
replace it with a shorter adapter or no adapter, you must remove the
full-length-adapter bracket from the end of the riser-card assembly and return the
bracket to its storage location.
To remove and store the full-length-adapter bracket, complete the following steps:
1. Press the bracket tab
3
and slide the bracket to the left until the bracket falls
free of the riser-card assembly.
2. Align the bracket with the storage location on the riser-card assembly as shown.
3. Place the two hooks
1
in the two openings
2
in the storage location on the
riser-card assembly.
4. Press the bracket tab
3
and slide the bracket toward the
expansion-slot-opening end of the assembly until the bracket clicks into place.
5. Return to “Installing a PCI adapter in a PCI riser-card assembly” on page 171 or
“Installing a PCI riser-card assembly” on page 168, as applicable.
184
ThinkServer RD220 Types 3729, 3779, 3797, and 3798: Hardware Maintenance Manual
Содержание THINKSERVER 3729
Страница 1: ...Hardware Maintenance Manual ThinkServer RD220 Types 3797 3798 3779 and 3729 ...
Страница 2: ......
Страница 3: ...ThinkServer RD220 Types 3729 3779 3797 and 3798 Hardware Maintenance Manual ...
Страница 8: ...vi ThinkServer RD220 Types 3729 3779 3797 and 3798 Hardware Maintenance Manual ...
Страница 156: ...148 ThinkServer RD220 Types 3729 3779 3797 and 3798 Hardware Maintenance Manual ...
Страница 238: ...230 ThinkServer RD220 Types 3729 3779 3797 and 3798 Hardware Maintenance Manual ...
Страница 262: ...Japanese recycling statements 254 ThinkServer RD220 Types 3729 3779 3797 and 3798 Hardware Maintenance Manual ...
Страница 264: ...256 ThinkServer RD220 Types 3729 3779 3797 and 3798 Hardware Maintenance Manual ...
Страница 265: ......
Страница 266: ...Part Number 40M2493 Printed in USA 1P P N 40M2493 ...