background image

Page 8

ZH 036, 048, 060

BLOWER ASSEMBLY

TO INCREASE BELT TENSION

1-Loosen four bolts securing motor base to mounting frame.

2-Slide the motor downward to tighten the belt.

3-Tighten four bolts on motor base.

TO INCREASE CFM

LOOSEN ALLEN SCREW &

TURN PULLEY CLOCKWISE

TO DECREASE CFM

TURN PULLEY

COUNTERCLOCKWISE

FIGURE 10

PULLEY

MOTOR

SIDE VIEW

ALLEN

SCREW

LOOSEN FOUR BOLTS

AND SLIDE BLOWER

MOTOR DOWNWARD

TO TIGHTEN BELT

FIGURE 11

PULLEY ALIGNMENT

BELT

MOTOR

PULLEY

BLOWER

PULLEY

NOT ALIGNED

ALIGNED

1- Loosen four bolts securing motor base to mounting

frame. See figure 10.

2-

To increase belt tension -

Slide blower motor downward to tighten the belt. This
increases the distance between the blower motor and
the blower housing.

To loosen belt tension -

Slide blower motor upward to loosen the belt. This
decreases the distance between the blower motor
and the blower housing.

3- Tighten four bolts securing motor base to the

mounting frame.

D - Check Belt Tension

Overtensioning belts shortens belt and bearing life.
Check belt tension as follows:

1- Measure span length X. See figure 12.

2- Apply perpendicular force to center of span (X) with

enough pressure to deflect belt 1/64” for every inch
of span length or 1.5mm per 100mm of span length.

Example: Deflection distance of a 40” span would be
40/64” or 5/8”.

Example: Deflection distance of a 400mm span
would be 6mm.

3- Measure belt deflection force. For a used belt, the

deflection force should be 5 lbs. (35kPa). A new belt
deflection force should be 7 lbs. (48kPa).

A force below these values indicates an
undertensioned belt. A force above these values
indicates an overtensioned belt.

MEASURE BELT TENSION

FIGURE 12

DEFLECTION 1/64” PER INCH OF SPAN

OR 1.5mm PER 100mm OF SPAN

FORCE

E-Field-Furnished Blower Drives

For field-furnished blower drives, use pages 9-14 to

determine BHP and RPM required. Reference page 15

for additional air resistance and drive kit numbers. See

table 2 for drive component manufacturer's numbers.

Содержание ZHA036

Страница 1: ...ng and Packing List Page 3 General Page 3 Requirements Page 3 Unit Support Page 4 Duct Connection Page 4 INSTALLATION INSTRUCTIONS ZHA036 3 TON ZHB036 3 TON ZHA048 4 TON ZHB048 4 TON ZHA060 5 TON ZHB0...

Страница 2: ...937 ZHA036 046 44 7 8 1140 ZH 060 ZHB036 048 10 7 8 276 25 5 8 651 5 1 8 130 75 7 8 1927 TOP VIEW Base 24 9 16 624 12 1 8 308 5 1 8 130 BOTTOM SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 17 3 4 451...

Страница 3: ...contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to swell Bubbles in the rubber roofing material can cause leaks Protect the roof surface to avoid expo...

Страница 4: ...ny form of moisture from entering unit Recommended minimum frame height is 14 356mm 4 Duct must be attached to the roof mounting frame and not to the unit Supply and return plenums must be installed b...

Страница 5: ...CONE SEALANT BETWEEN DUCT COVER FLANGE AND UNIT INSULATION NOT TO SCALE 4 Install return air duct on the intake air side of the horizontal economizer See figure 5 5 Horizontal economizer and return ai...

Страница 6: ...thermostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys IMPORTANT Unless f...

Страница 7: ...gure 9 Note Static pressure readings can vary if not taken where shown 3 Measure the indoor blower wheel RPM 4 Referring to pages 9 14 use static pressure and RPM readings to determine unit CFM Use op...

Страница 8: ...ten four bolts securing motor base to the mounting frame D Check Belt Tension Overtensioning belts shortens belt and bearing life Check belt tension as follows 1 Measure span length X See figure 12 2...

Страница 9: ...47 0 56 1287 0 6 1326 0 64 1364 0 68 1402 0 72 1300 1139 0 51 1182 0 55 1224 0 58 1265 0 62 1304 0 66 1342 0 71 1379 0 75 1416 0 79 1400 1160 0 57 1202 0 61 1243 0 65 1283 0 69 1322 0 73 1359 0 78 139...

Страница 10: ...5 0 92 1382 0 97 1417 1 02 1452 1 07 1486 1 11 1800 1253 0 85 1292 0 91 1331 0 96 1368 1 01 1404 1 06 1439 1 11 1473 1 16 1506 1 21 1900 1279 0 94 1317 1 00 1355 1 05 1392 1 10 1427 1 16 1461 1 21 149...

Страница 11: ...422 1 28 1456 1 34 1489 1 40 1521 1 45 1554 1 50 2200 1341 1 22 1378 1 28 1414 1 34 1448 1 41 1481 1 46 1513 1 52 1546 1 57 1578 1 62 2300 1371 1 34 1407 1 41 1442 1 47 1475 1 54 1507 1 59 1539 1 65 1...

Страница 12: ...1231 0 54 1271 0 58 1310 0 62 1347 0 66 1385 0 69 1300 1115 0 50 1161 0 53 1204 0 56 1246 0 60 1286 0 64 1325 0 68 1362 0 72 1399 0 76 1400 1135 0 56 1179 0 59 1222 0 62 1264 0 66 1303 0 70 1341 0 75...

Страница 13: ...1335 0 94 1375 0 98 1413 1 02 1449 1 07 1485 1 12 1800 1233 0 91 1276 0 94 1318 0 98 1358 1 02 1397 1 06 1434 1 11 1469 1 16 1504 1 21 1900 1261 0 98 1303 1 02 1343 1 06 1382 1 11 1420 1 16 1455 1 21...

Страница 14: ...944 1 15 971 1 22 997 1 28 1022 1 34 1046 1 40 1070 1 46 2200 902 1 13 931 1 19 959 1 24 986 1 31 1012 1 37 1036 1 43 1060 1 50 1084 1 56 2300 920 1 23 948 1 29 975 1 35 1001 1 41 1027 1 47 1051 1 53...

Страница 15: ...15 1 5 1 7 ZA03 906 1383 2 ZA06 1262 1634 ZHB060 1 1 1 1 15 1 5 1 7 ZAA01 522 784 ZAA02 632 875 2 ZAA03 798 1105 NOTE Using total air volume and system static pressure requirements determine from blow...

Страница 16: ...tional Electric Heat An increased heating demand W2 will energize electric heat Electric heat is also energized during the defrost cycle W1 to maintain discharge air temperature Cooling 1 Set thermost...

Страница 17: ...charge Note that suction pressure can change as charge is adjusted 7 Example ZHA036 At 95 F outdoor ambient and a measured suction pressure of 130psig the target liquid temperature is 105 5 F For a m...

Страница 18: ...105 F 115 F Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig 119 236 122 274 125 315 128 361 130 410 133 464 126 239 128 278 132...

Страница 19: ...100 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHA048 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction Pres...

Страница 20: ...0 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHB 036 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Outdoor Temper...

Страница 21: ...100 110 120 130 110 120 130 140 150 160 170 Suction Pressure psig 105 95 115 85 75 65 180 Outdoor Temperature F 60 ZHB060 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction P...

Страница 22: ...ting The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered If the timing jumper is in the TEST position at power up the defrost control...

Страница 23: ...psig DO NOT REPLACE COMPRESSOR C Filters Units are equipped with temporary filters which must be replaced prior to building occupation See table 11 for correct filter size Refer to local codes or app...

Страница 24: ...rmed slabs On units with two slabs dirt and debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 16 Flush coils with wat...

Отзывы: