background image

Page 16

ZH 036, 048, 060

TABLE 2

DRIVE COMPONENT MANUFACTURER'S NUMBERS

Drive No.

DRIVE COMPONENT PART NUMBERS

Motor Pulley

Blower Pulley

Belts

Browning

OEM

Browning

OEM

Browning

OEM

Z01

1VP34 X 7/8

31K6901

AK54 X 5/8

100244­30

A40

100245­17

Z02

1VP34 X 7/8

31K6901

AK46 X 5/8

100244­31

A39

100245­16

Z03

1VP34 X 7/8

31K6901

AK41 X 5/8

100244­28

A39

100245­16

Z04

1VP34 X 7/8

31K6901

AK39 X 5/8

100244­32

A38

100245­15

Z05

1VP44 X 7/8

P­8­1488

AK49 X 5/8

100244­26

A41

100245­18

Z06

1VP50 X 7/8

53J1501

AK51 X 5/8

100244­29

A42

100245­19

ZAA01

1VP34 X 7/8

31K69

AK69 X 1

37L47

AX51

13H01

ZAA02

1VP40 X 7/8

79J03

BK80H

100788-03

A53

100245-40

ZAA03

1VP40 X 7/8

79J03

AK59 X 1

31K68

A50

100245-29

TABLE 3

MINIMUM AIRFLOW - UNITS WITH ELECTRIC HEAT

kW

CFM - Downflow and Horizontal

ZHA036-060, ZHB036-048

ZHB060

5

960

1750

7.5

960

1750

10

960

1750

15

960

1750

22.5

1280

1750

Units with electric heat (5-22.5kW) can operate up to 1.6”w.g. maximum static pressure.

Start-Up

IMPORTANT

This unit is equipped with a crankcase heater. Make
sure heater is energized 24 hours before unit start-
up to prevent compressor damage as a result of
slugging.

A-Start-Up

Heating

1- Set thermostat or temperature control device to

initiate a first-stage heating demand.

2- A first-stage heating demand (W1) will energize

compressors 1 and the outdoor fan.

Note - L1 reversing valve is de-energized in the
heating mode.

ZH Units With Optional Electric Heat -

An increased heating demand (W2) will energize
electric heat. Electric heat is also energized during
the defrost cycle (W1) to maintain discharge air
temperature.

Cooling

1- Set thermostat or temperature control device fan

switch to 

AUTO

 or 

ON.

 Set thermostat or

temperature control device to initiate a first-stage
cooling demand.

A first-stage Y1 cooling demand will energize L1
reversing valve solenoid and compressor 1.

Units With Optional Economizer 

-

The optional economizer will start on a first stage (Y1)
cooling demand when outdoor air is suitable. An
increased cooling demand (Y2) will energize
compressor 1.

2- Refrigerant circuits are factory charged with R-410A

refrigerant. See unit rating plate for correct amount of
charge.

B-Three Phase Scroll Compressor Voltage Phasing

Three phase scroll compressors must be phased
sequentially to ensure correct compressor and blower
rotation and operation. Compressor and blower are
wired in phase at the factory. Power wires are
color-coded as follows: line 1-red, line 2-yellow, line
3-blue.

1- Observe suction and discharge pressures and

blower rotation on unit start-up.

2- Suction pressure must drop, discharge pressure

must rise, and blower rotation must match rotation
marking.

If pressure differential is not observed or blower rotation is
not correct:

3- Disconnect all remote electrical power supplies.
4- Reverse any two field-installed wires connected to

the line side of K1 contactor. Do not reverse wires at
blower contactor.

Make sure the connections are tight.

Discharge and suction pressures should operate at
their normal start‐up ranges.

Содержание ZHA036

Страница 1: ...ng and Packing List Page 3 General Page 3 Requirements Page 3 Unit Support Page 4 Duct Connection Page 4 INSTALLATION INSTRUCTIONS ZHA036 3 TON ZHB036 3 TON ZHA048 4 TON ZHB048 4 TON ZHA060 5 TON ZHB0...

Страница 2: ...937 ZHA036 046 44 7 8 1140 ZH 060 ZHB036 048 10 7 8 276 25 5 8 651 5 1 8 130 75 7 8 1927 TOP VIEW Base 24 9 16 624 12 1 8 308 5 1 8 130 BOTTOM SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 17 3 4 451...

Страница 3: ...contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to swell Bubbles in the rubber roofing material can cause leaks Protect the roof surface to avoid expo...

Страница 4: ...ny form of moisture from entering unit Recommended minimum frame height is 14 356mm 4 Duct must be attached to the roof mounting frame and not to the unit Supply and return plenums must be installed b...

Страница 5: ...CONE SEALANT BETWEEN DUCT COVER FLANGE AND UNIT INSULATION NOT TO SCALE 4 Install return air duct on the intake air side of the horizontal economizer See figure 5 5 Horizontal economizer and return ai...

Страница 6: ...thermostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys IMPORTANT Unless f...

Страница 7: ...gure 9 Note Static pressure readings can vary if not taken where shown 3 Measure the indoor blower wheel RPM 4 Referring to pages 9 14 use static pressure and RPM readings to determine unit CFM Use op...

Страница 8: ...ten four bolts securing motor base to the mounting frame D Check Belt Tension Overtensioning belts shortens belt and bearing life Check belt tension as follows 1 Measure span length X See figure 12 2...

Страница 9: ...47 0 56 1287 0 6 1326 0 64 1364 0 68 1402 0 72 1300 1139 0 51 1182 0 55 1224 0 58 1265 0 62 1304 0 66 1342 0 71 1379 0 75 1416 0 79 1400 1160 0 57 1202 0 61 1243 0 65 1283 0 69 1322 0 73 1359 0 78 139...

Страница 10: ...5 0 92 1382 0 97 1417 1 02 1452 1 07 1486 1 11 1800 1253 0 85 1292 0 91 1331 0 96 1368 1 01 1404 1 06 1439 1 11 1473 1 16 1506 1 21 1900 1279 0 94 1317 1 00 1355 1 05 1392 1 10 1427 1 16 1461 1 21 149...

Страница 11: ...422 1 28 1456 1 34 1489 1 40 1521 1 45 1554 1 50 2200 1341 1 22 1378 1 28 1414 1 34 1448 1 41 1481 1 46 1513 1 52 1546 1 57 1578 1 62 2300 1371 1 34 1407 1 41 1442 1 47 1475 1 54 1507 1 59 1539 1 65 1...

Страница 12: ...1231 0 54 1271 0 58 1310 0 62 1347 0 66 1385 0 69 1300 1115 0 50 1161 0 53 1204 0 56 1246 0 60 1286 0 64 1325 0 68 1362 0 72 1399 0 76 1400 1135 0 56 1179 0 59 1222 0 62 1264 0 66 1303 0 70 1341 0 75...

Страница 13: ...1335 0 94 1375 0 98 1413 1 02 1449 1 07 1485 1 12 1800 1233 0 91 1276 0 94 1318 0 98 1358 1 02 1397 1 06 1434 1 11 1469 1 16 1504 1 21 1900 1261 0 98 1303 1 02 1343 1 06 1382 1 11 1420 1 16 1455 1 21...

Страница 14: ...944 1 15 971 1 22 997 1 28 1022 1 34 1046 1 40 1070 1 46 2200 902 1 13 931 1 19 959 1 24 986 1 31 1012 1 37 1036 1 43 1060 1 50 1084 1 56 2300 920 1 23 948 1 29 975 1 35 1001 1 41 1027 1 47 1051 1 53...

Страница 15: ...15 1 5 1 7 ZA03 906 1383 2 ZA06 1262 1634 ZHB060 1 1 1 1 15 1 5 1 7 ZAA01 522 784 ZAA02 632 875 2 ZAA03 798 1105 NOTE Using total air volume and system static pressure requirements determine from blow...

Страница 16: ...tional Electric Heat An increased heating demand W2 will energize electric heat Electric heat is also energized during the defrost cycle W1 to maintain discharge air temperature Cooling 1 Set thermost...

Страница 17: ...charge Note that suction pressure can change as charge is adjusted 7 Example ZHA036 At 95 F outdoor ambient and a measured suction pressure of 130psig the target liquid temperature is 105 5 F For a m...

Страница 18: ...105 F 115 F Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig 119 236 122 274 125 315 128 361 130 410 133 464 126 239 128 278 132...

Страница 19: ...100 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHA048 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction Pres...

Страница 20: ...0 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHB 036 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Outdoor Temper...

Страница 21: ...100 110 120 130 110 120 130 140 150 160 170 Suction Pressure psig 105 95 115 85 75 65 180 Outdoor Temperature F 60 ZHB060 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction P...

Страница 22: ...ting The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered If the timing jumper is in the TEST position at power up the defrost control...

Страница 23: ...psig DO NOT REPLACE COMPRESSOR C Filters Units are equipped with temporary filters which must be replaced prior to building occupation See table 11 for correct filter size Refer to local codes or app...

Страница 24: ...rmed slabs On units with two slabs dirt and debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 16 Flush coils with wat...