BLOWER DATA

POWER EXHAUST FAN PERFORMANCE

 Return Air System Static Pressure - in. w.g. 

Air Volume Exhausted 

cfm

0.00

1865

0.05

1785

0.10

1710

0.15

1630

0.20

1545

0.25

1450

0.30

1350

0.35

1240

CEILING DIFFUSER AIR THROW DATA

Air Volume - cfm

1

 Effective Throw - ft.

Model No.

RTD9-65

FD9-65

800

10 - 17

14 - 18

1000

10 - 17

15 - 20

1200

11 - 18

16 - 22

1400

12 - 19

17 - 24

1600

12 - 20

18 - 25

1800

13 - 21

20 - 28

2000

14 - 23

21 - 29

2200

16 - 25

22 - 30

1

 Effective throw based on terminal velocities of 75 ft. per minute.

CEILING DIFFUSERS AIR RESISTANCE (in. w.g.)

Air Volume 

cfm

RTD9-65 Step-Down Diffuser

FD9-65 

Flush 

Diffuser

2 Ends 

Open

1 Side & 

2 Ends Open

All Ends & 

Sides Open

800

0.15

0.13

0.11

0.11

1000

0.19

0.16

0.14

0.14

1200

0.25

0.20

0.17

0.17

1400

0.33

0.26

0.20

0.20

1600

0.43

0.32

0.20

0.24

1800

0.56

0.40

0.30

0.30

2000

0.73

0.50

0.36

0.36

2200

0.95

0.63

0.44

0.44

DRIVE KIT SPECIFICATIONS

Model No.

Blower Motor Choice (HP)

Drive Kit No.

RPM Range

Nominal

Maximum

Nominal

Maximum

ZHA/ZHB036

1

 1

1

 1.15

1.5

1.7

ZA01

678 - 1035

ZA04

964 - 1471

ZHA/ZHB048

1

 1

1

 1.15

1.5

1.7

ZA02

803 - 1226

2

 ZA05

1098 - 1490

ZHA060

1

 1

1

 1.15

1.5

1.7

ZA03

906-1383

2

 ZA06

1262-1634

ZHB060

1

 1

1

 1.15

1.5

1.7

ZAA01

522 - 784

ZAA02

632 - 875

ZAA03

798 - 1105

NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of 

motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp are used, be sure to keep within the service 

factor limitations outlined on the motor nameplate.

1

 1 hp blower motor is not available for 208/230V-1ph applications.     

1.5 hp motor is required with ZA05, ZA06 and ZAA03 drive kits.

OPTIONS / ACCESSORIES AIR RESISTANCE - in. w.g. 

Air Volume 

cfm

Wet Indoor Coil

Electric 

Heat

Economizer

ZHA036, ZHA048

ZHA060, ZHB036

ZHB048, ZHB060

Downflow

Horizontal

900

0.01

0.01

- - -

0.05

0.03

0.04

1000

0.02

0.01

- - -

0.06

0.03

0.05

1100

0.02

0.02

- - -

0.08

0.04

0.05

1200

0.02

0.02

0.01

0.09

0.05

0.06

1300

0.03

0.02

0.02

0.12

0.05

0.07

1400

0.03

0.03

0.02

0.17

0.06

0.08

1500

0.04

0.03

0.02

0.22

0.07

0.08

1600

0.04

0.03

0.03

0.26

0.08

0.09

1700

0.05

0.04

0.03

0.30

0.09

0.10

1800

0.05

0.04

0.03

0.33

0.10

0.11

1900

0.06

0.05

0.04

0.33

0.11

0.12

2000

0.06

0.05

0.04

0.31

0.12

0.13

2100

- - -

0.06

0.05

0.27

0.13

0.14

2200

- - -

0.06

0.05

0.29

0.14

0.15

2300

- - -

0.07

0.05

0.31

0.15

0.16

2400

- - -

0.07

0.06

0.32

0.16

0.18

Содержание ZHA036

Страница 1: ...ng and Packing List Page 3 General Page 3 Requirements Page 3 Unit Support Page 4 Duct Connection Page 4 INSTALLATION INSTRUCTIONS ZHA036 3 TON ZHB036 3 TON ZHA048 4 TON ZHB048 4 TON ZHA060 5 TON ZHB0...

Страница 2: ...937 ZHA036 046 44 7 8 1140 ZH 060 ZHB036 048 10 7 8 276 25 5 8 651 5 1 8 130 75 7 8 1927 TOP VIEW Base 24 9 16 624 12 1 8 308 5 1 8 130 BOTTOM SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 17 3 4 451...

Страница 3: ...contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to swell Bubbles in the rubber roofing material can cause leaks Protect the roof surface to avoid expo...

Страница 4: ...ny form of moisture from entering unit Recommended minimum frame height is 14 356mm 4 Duct must be attached to the roof mounting frame and not to the unit Supply and return plenums must be installed b...

Страница 5: ...CONE SEALANT BETWEEN DUCT COVER FLANGE AND UNIT INSULATION NOT TO SCALE 4 Install return air duct on the intake air side of the horizontal economizer See figure 5 5 Horizontal economizer and return ai...

Страница 6: ...thermostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys IMPORTANT Unless f...

Страница 7: ...gure 9 Note Static pressure readings can vary if not taken where shown 3 Measure the indoor blower wheel RPM 4 Referring to pages 9 14 use static pressure and RPM readings to determine unit CFM Use op...

Страница 8: ...ten four bolts securing motor base to the mounting frame D Check Belt Tension Overtensioning belts shortens belt and bearing life Check belt tension as follows 1 Measure span length X See figure 12 2...

Страница 9: ...47 0 56 1287 0 6 1326 0 64 1364 0 68 1402 0 72 1300 1139 0 51 1182 0 55 1224 0 58 1265 0 62 1304 0 66 1342 0 71 1379 0 75 1416 0 79 1400 1160 0 57 1202 0 61 1243 0 65 1283 0 69 1322 0 73 1359 0 78 139...

Страница 10: ...5 0 92 1382 0 97 1417 1 02 1452 1 07 1486 1 11 1800 1253 0 85 1292 0 91 1331 0 96 1368 1 01 1404 1 06 1439 1 11 1473 1 16 1506 1 21 1900 1279 0 94 1317 1 00 1355 1 05 1392 1 10 1427 1 16 1461 1 21 149...

Страница 11: ...422 1 28 1456 1 34 1489 1 40 1521 1 45 1554 1 50 2200 1341 1 22 1378 1 28 1414 1 34 1448 1 41 1481 1 46 1513 1 52 1546 1 57 1578 1 62 2300 1371 1 34 1407 1 41 1442 1 47 1475 1 54 1507 1 59 1539 1 65 1...

Страница 12: ...1231 0 54 1271 0 58 1310 0 62 1347 0 66 1385 0 69 1300 1115 0 50 1161 0 53 1204 0 56 1246 0 60 1286 0 64 1325 0 68 1362 0 72 1399 0 76 1400 1135 0 56 1179 0 59 1222 0 62 1264 0 66 1303 0 70 1341 0 75...

Страница 13: ...1335 0 94 1375 0 98 1413 1 02 1449 1 07 1485 1 12 1800 1233 0 91 1276 0 94 1318 0 98 1358 1 02 1397 1 06 1434 1 11 1469 1 16 1504 1 21 1900 1261 0 98 1303 1 02 1343 1 06 1382 1 11 1420 1 16 1455 1 21...

Страница 14: ...944 1 15 971 1 22 997 1 28 1022 1 34 1046 1 40 1070 1 46 2200 902 1 13 931 1 19 959 1 24 986 1 31 1012 1 37 1036 1 43 1060 1 50 1084 1 56 2300 920 1 23 948 1 29 975 1 35 1001 1 41 1027 1 47 1051 1 53...

Страница 15: ...15 1 5 1 7 ZA03 906 1383 2 ZA06 1262 1634 ZHB060 1 1 1 1 15 1 5 1 7 ZAA01 522 784 ZAA02 632 875 2 ZAA03 798 1105 NOTE Using total air volume and system static pressure requirements determine from blow...

Страница 16: ...tional Electric Heat An increased heating demand W2 will energize electric heat Electric heat is also energized during the defrost cycle W1 to maintain discharge air temperature Cooling 1 Set thermost...

Страница 17: ...charge Note that suction pressure can change as charge is adjusted 7 Example ZHA036 At 95 F outdoor ambient and a measured suction pressure of 130psig the target liquid temperature is 105 5 F For a m...

Страница 18: ...105 F 115 F Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig 119 236 122 274 125 315 128 361 130 410 133 464 126 239 128 278 132...

Страница 19: ...100 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHA048 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction Pres...

Страница 20: ...0 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHB 036 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Outdoor Temper...

Страница 21: ...100 110 120 130 110 120 130 140 150 160 170 Suction Pressure psig 105 95 115 85 75 65 180 Outdoor Temperature F 60 ZHB060 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction P...

Страница 22: ...ting The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered If the timing jumper is in the TEST position at power up the defrost control...

Страница 23: ...psig DO NOT REPLACE COMPRESSOR C Filters Units are equipped with temporary filters which must be replaced prior to building occupation See table 11 for correct filter size Refer to local codes or app...

Страница 24: ...rmed slabs On units with two slabs dirt and debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 16 Flush coils with wat...

Отзывы: