background image

7

Installation

It is important to locate the unit where it can be accessed 

for service in the future. Refer to unit dimensions on Pages 

3-5 for exact locations of suspension brackets, return air 

and supply air openings.

1.  Make sure that the structural ceiling or slab is able 

to support the weight of the indoor unit. It may be 

necessary to add extra support. 

2.  Install suspension rods in the structural 

ceiling or concrete slab in a suitable location. 

 

If the structural ceiling is constructed of concrete, 

install  anchors  to  accept  four  ⅜”  threaded  rods  to 

suspend the indoor unit. If the structural ceiling 

includes wooden joists, use angle iron or Unistrut 

channel  fixed  securely  in  place  to  accept  the  ⅜” 

threaded rods. 

NOTE - 

Threaded rod (requirement 

of Lennox warranty program) is the ONLY acceptable 

method of suspending the unit; do not use chains or 

straps.  

See Figure 2.

3.  Slide one nut and one washer onto each threaded rod. 

Use electrical tape to keep the washer from failing off. 

Position the nuts slightly above the final resting place 

of the four suspension brackets. See Figure 3.

Figure 2. Suspending Methods

ANGLE IRON

BOLTED IN

PLACE ACROSS

WOODEN JOISTS

WOODEN JOIST

⅜”  THREADE

D

ROD

ANGLE IRON

ACROSS

WOODEN JOISTS

ANCHOR

CONCRETE CEILING

USING ANCHORS

⅜”  THREADE

D

ROD

4.  Use either a mechanical lifting device or a minimum of 

two people to raise the unit and insert the threaded rods 

into the suspension brackets on the unit base. Slide 

a washer and then a nut onto each rod below each 

suspension bracket. Use the leveling nut (beneath 

suspension bracket) to adjust the unit to the correct 

height. Remove the electrical tape holding the upper 

washers and nuts in place and tighten each of the four 

nuts above the brackets down onto the brackets. This 

will ensure that the unit remains level.

5. 

It is recommended to install a field-provided isolation 

grommet as shown in Figure 4 to prevent transmission 

of vibration from unit to structural ceiling.

6.  If the unit is being installed in an application that includes 

a sheet rock (plasterboard) ceiling, it is required that 

an access panel be installed in a suitable location. 

This will also allow access for future maintenance 

(requirement  of  Lennox  warranty  program).

 

Access is required during the commissioning process 

to test the condensate disposal system and to check 

the local disconnect.

7. 

The unit is factory-configured for the supply air to be 

delivered from the front and the return air filter at the 

rear of the unit. 

INSTALLATION GUIDELINES

• 

It is recommended to install a field-provided isolation 

grommet as shown in Figure 4 to prevent transmission 

of vibration from unit to structural ceiling.

•  Provide separate support for the weight of the duct 

system. Duct system must not be supported by the 

indoor unit.

• 

Use flexible joints (canvas) at the point where the duct 

connects to the unit on both ends. Material must meet 

all local and national code requirements.

•  When unit is being installed in a location where even 

the slightest noise would be a problem (meeting room 

or other very quiet space), design duct system to avoid 

transmission of vibration to the structure to the extent 

possible.

• 

When  sizing  the  return  air  filter  grille,  a  minimum 

surface area of 200 sq. in. per ton is recommended.

LEVELING

NUT

” THREADED

ROD

SUSPENSION

BRACKET

FIELD-PROVIDED

ISOLATION GROMMET

WASHER

INDOOR UNIT

LEVELING

NUT

” THREADED

ROD

SUSPENSION

BRACKET

SUPPLY AIR

OPENING

FRONT VIEW

When unit is

level, tighten

nut to secure

position of

suspension

bracket on

rod.

Figure 3. Suspension Hardware

Figure 4. Isolation Grommet

Содержание VOSB Series

Страница 1: ...oss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow safety warnings and these instruc tions exactly c...

Страница 2: ...cations department When the indicated lengths change from the figures stated within the report it is imperative that prior to the commencement of the refrigerant pipe work installation Lennox VRF appl...

Страница 3: ...ETURN AIR DUCT OPENING SUPPLY AIR DUCT OPENING RIGHT SIDE VIEW LIQUID PIPE GAS PIPE AIR FLOW SECTION B B SUPPLY AIR DUCT OPENING AUXILIARY DRAIN CONNECTION Either Side PRIMARY DRAIN CONNECTION Either...

Страница 4: ...IR DUCT OPENING 6 152 36 7 8 937 Supply Air Duct Opening 2 51 14 7 8 378 38 1 4 972 34 5 8 879 19 7 8 505 2 3 4 70 3 76 44 1 8 1120 13 1 2 343 38 1 4 972 32 7 8 835 56 3 4 1441 50 1270 12 1 8 308 5 1...

Страница 5: ...Minimum Clearance Ceiling Wall Wall 1 25 mm Minimum Clearance Ceiling Suspended Minimum Service Clearance Figure 1 Minimum Installation Clearances NOTE No part of the suspended ceiling or other suppo...

Страница 6: ...line radio telephone security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation WARNING Do not install the unit in an area where flammabl...

Страница 7: ...tighten each of the four nuts above the brackets down onto the brackets This will ensure that the unit remains level 5 It is recommended to install a field provided isolation grommet as shown in Figu...

Страница 8: ...ut Filter Filter removal tab 3 Reverse these steps to reinstall the filter Be sure to reinstall the receiver if it was detached during the filter removal Figure 8 Filter Partially Removed Indoor Unit...

Страница 9: ...for leaks per commissioning instructions WARNING WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing Ap...

Страница 10: ...refrigerant line ports 3 Slowly loosen one of the rubber plugs to release the factory nitrogen charge Remove the rubber plug from both liquid and gas lines 4 Connect the liquid and gas lines to the ev...

Страница 11: ...drain piping is properly routed and insulatedinordertopreventbothleaksandcondensation Follow these instructions exactly to ensure proper drainage and unit operation IMPORTANT You must confirm operati...

Страница 12: ...spension Rods 3 ft 1 m Support straps NOTE Drain line should be sloped 1 4 inch per foot 18 mm per m AWAY from unit and should be supported as needed to prevent sagging Do not overtighten drain fittin...

Страница 13: ...tight to avoid strain on wiring Insecure wiring connections may result in equipment failure and risk of fire Wiring must be installed so that all cover plates can be securely closed Do not attempt to...

Страница 14: ...230V 1Ph 60Hz Power supply Mode Selection Box Indoor unit Indoor unit Indoor unit Dedicated breaker Service Disconnect L1 L2 L1 L2 Fuse Service Disconnect L1 L2 Fuse Service Disconnect L1 L2 Fuse Serv...

Страница 15: ...polarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor...

Страница 16: ...Terminal Block HA HB 12V COM P Q Ground cable shield to Indoor Unit chassis Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the terminal sc...

Страница 17: ...valve XT1 2 PUMP CS ALARM SVD Solenoid valve Code Title T2B E U L B T2A WHITE T1 T0 RED ACK L B TA C A L B K T2 Outlet air temperature sensor To wired controller power Display Board NOTE Component in...

Страница 18: ...ntent E0 E1 E2 E4 E5 Mode conflict Communication error between indoor and main outdoor unit T0 Inlet air temperature sensor malfunction TA Outlet airtemperature sensor malfunction T2B Outlet of evapor...

Страница 19: ...o the black wire on each end or use the VRF accessory V0SNSR00P 13G99 to splice in the extension cable 6 Locate the return air thermistor to the conditioned area of which the indoor unit serves Figure...

Страница 20: ...function T2B Outlet of evaporator sensor malfunction T2A Inlet of evaporator sensor malfunction Error Content Error code FE Eb U4 Ed EE F8 No address EEV malfunction MS self inspection error Outdoor u...

Страница 21: ...fixed plastic mounting brackets on the back of the receiver Figure 26 into the two slots on the bottom of the electrical control box Figure 25 and slide to secure it 3 Connect the 10 conductor wire o...

Страница 22: ...emote controller No Content Recorded Value Date 0 Normal display 1 Communication address of indoor unit 2 Indoor unit capacity horsepower 3 Network address of indoor unit 4 The actual setpoint tempera...

Страница 23: ...er power has been broken and restored at the disconnect switch or circuit breaker call VRF Technical Support 1 844 438 8731 Error Code Description FE No address E0 Mode conflict E1 Communication error...

Страница 24: ...24 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Отзывы: