NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
RATINGS
10 TON (DUAL CIRCUIT)
TS 6 to 20 Ton R−410A Air Conditioners
AIR HANDLERS
COOLING CAPACITY − TSA120S4D (FIRST STAGE) with
[TAA120S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
65
_
F (18
_
C)
75
_
F (24
_
C)
85
_
F (29
_
C)
95
_
F (35
_
C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm
L/s
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh
kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
63
_
F
(17
_
C)
3200
1510
61.7
18.1
2.72
.65
.78
.94
59.4
17.4
3.08
.66
.80
.96
56.8
16.6
3.49
.67
.82
.99
54.2
15.9
3.95
.68
.85
1.00
4000
1890
64.7
19.0
2.76
.69
.87
1.00
62.1
18.2
3.11
.70
.89
1.00
59.4
17.4
3.52
.72
.92
1.00
56.6
16.6
3.97
.74
.95
1.00
4800
2265
66.9
19.6
2.79
.74
.95
1.00
64.3
18.8
3.14
.76
.97
1.00
61.6
18.1
3.55
.78
.99
1.00
58.7
17.2
4.01
.81
1.00
1.00
67
_
F
(19
_
C)
3200
1510
65.3
19.1
2.77
.52
.62
.74
62.8
18.4
3.12
.52
.63
.75
60.2
17.6
3.53
.53
.64
.78
57.5
16.9
3.99
.54
.66
.80
4000
1890
68.5
20.1
2.80
.54
.67
.82
65.7
19.3
3.16
.55
.68
.84
62.8
18.4
3.56
.55
.69
.87
59.9
17.6
4.03
.57
.71
.91
4800
2265
70.6
20.7
2.83
.56
.71
.91
67.8
19.9
3.19
.57
.73
.93
64.8
19.0
3.59
.59
.76
.96
61.6
18.1
4.04
.59
.78
.99
71
_
F
(22
_
C)
3200
1510
68.9
20.2
2.81
.40
.50
.60
66.3
19.4
3.17
.40
.51
.61
63.5
18.6
3.57
.40
.51
.62
60.7
17.8
4.04
.40
.52
.64
4000
1890
72.2
21.2
2.84
.41
.53
.65
69.3
20.3
3.21
.41
.54
.66
66.2
19.4
3.61
.41
.54
.67
63.2
18.5
4.07
.41
.56
.69
4800
2265
74.4
21.8
2.87
.41
.55
.69
71.5
21.0
3.24
.42
.56
.71
68.3
20.0
3.64
.42
.58
.73
65.0
19.0
4.10
.43
.59
.75
COOLING CAPACITY − TSA120S4D (SECOND STAGE) with
[TAA120S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85
_
F (29
_
C)
95
_
F (35
_
C)
105
_
F (41
_
C)
115
_
F (46
_
C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm
L/s
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh
kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
63
_
F
(17
_
C)
3200
1510 113.6 33.3
6.99
.67
.82
.99
108.2
31.7
7.91
.68
.85
1.00
102.5 30.0
8.99
.69
.88
1.00
96.4
28.3
10.22
.72
.92
1.00
4000
1890 118.9 34.8
7.04
.72
.92
1.00
113.1
33.1
7.95
.74
.95
1.00
107.3 31.4
9.03
.77
.98
1.00
100.8 29.5
10.28
.80
1.00
1.00
4800
2265 123.1 36.1
7.10
.78
.99
1.00
117.3
34.4
8.02
.81
1.00
1.00
112.0 32.8
9.11
.84
1.00
1.00
105.6 30.9
10.37
.88
1.00
1.00
67
_
F
(19
_
C)
3200
1510 120.5 35.3
7.06
.53
.64
.78
114.9
33.7
7.99
.54
.66
.80
108.8 31.9
9.06
.54
.68
.84
102.4 30.0
10.30
.56
.70
.87
4000
1890 125.6 36.8
7.12
.56
.69
.87
119.7
35.1
8.06
.57
.71
.91
113.3 33.2
9.12
.58
.74
.94
105.9 31.0
10.34
.59
.77
.98
4800
2265 129.6 38.0
7.18
.59
.76
.96
123.2
36.1
8.09
.60
.78
.99
116.3 34.1
9.16
.61
.81
1.00
108.8 31.9
10.38
.63
.85
1.00
71
_
F
(22
_
C)
3200
1510 127.0 37.2
7.15
.40
.51
.62
121.3
35.5
8.08
.40
.52
.64
114.8 33.6
9.15
.41
.53
.65
108.0 31.7
10.39
.41
.54
.67
4000
1890 132.4 38.8
7.22
.41
.54
.67
126.5
37.1
8.15
.41
.56
.69
119.4 35.0
9.22
.42
.57
.71
112.1 32.9
10.45
.43
.58
.75
4800
2265 136.5 40.0
7.29
.42
.58
.73
129.9
38.1
8.21
.43
.59
.75
122.7 36.0
9.27
.43
.60
.78
115.1 33.7
10.52
.44
.63
.83
UP−FLOW INDOOR COIL
COOLING CAPACITY − TSA120S4D (FIRST STAGE) with
[(2) CX34−60D−6F]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
65
_
F (18
_
C)
75
_
F (24
_
C)
85
_
F (29
_
C)
95
_
F (35
_
C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm
L/s
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh
kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
63
_
F
(17
_
C)
3200
1510
59.2
17.3
2.70
.64
.77
.91
57.1
16.7
3.06
.65
.78
.93
54.9
16.1
3.47
.66
.80
.96
52.5
15.4
3.93
.67
.82
.99
4000
1890
62.3
18.3
2.73
.67
.83
.99
60.0
17.6
3.09
.68
.85
1.00
57.5
16.9
3.50
.70
.88
1.00
54.9
16.1
3.96
.72
.91
1.00
4800
2265
64.7
19.0
2.76
.71
.89
1.00
62.2
18.2
3.12
.73
.92
1.00
59.6
17.5
3.52
.75
.95
1.00
56.8
16.6
3.98
.77
.99
1.00
67
_
F
(19
_
C)
3200
1510
62.7
18.4
2.74
.52
.62
.73
60.5
17.7
3.10
.52
.63
.74
58.1
17.0
3.50
.53
.63
.76
55.5
16.3
3.96
.53
.65
.78
4000
1890
65.7
19.3
2.77
.53
.65
.79
63.4
18.6
3.13
.54
.66
.81
60.8
17.8
3.53
.55
.67
.84
58.0
17.0
4.00
.56
.69
.86
4800
2265
68.1
20.0
2.80
.55
.69
.85
65.4
19.2
3.16
.56
.69
.88
62.5
18.3
3.56
.57
.72
.91
59.8
17.5
4.02
.58
.74
.95
71
_
F
(22
_
C)
3200
1510
66.2
19.4
2.78
.40
.50
.59
63.8
18.7
3.14
.40
.50
.60
61.4
18.0
3.55
.40
.51
.61
58.6
17.2
4.01
.41
.52
.62
4000
1890
69.5
20.4
2.81
.41
.52
.63
67.0
19.6
3.18
.41
.53
.64
64.2
18.8
3.58
.41
.53
.66
61.2
17.9
4.04
.42
.54
.67
4800
2265
71.9
21.1
2.84
.42
.54
.67
69.2
20.3
3.21
.42
.55
.67
66.2
19.4
3.61
.42
.56
.70
63.1
18.5
4.08
.43
.57
.72
COOLING CAPACITY − TSA120S4D (SECOND STAGE) with
[(2) CX34−60D−6F]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85
_
F (29
_
C)
95
_
F (35
_
C)
105
_
F (41
_
C)
115
_
F (46
_
C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm
L/s
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh
kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
kBtuh kW
75
_
F
24
_
C
80
_
F
27
_
C
85
_
F
29
_
C
63
_
F
(17
_
C)
3200
1510 109.8 32.2
6.94
.66
.80
.96
104.9
30.7
7.86
.67
.82
.99
99.5
29.2
8.94
.68
.85
1.00
93.8
27.5
10.20
.70
.89
1.00
4000
1890 115.1 33.7
7.00
.70
.88
1.00
109.8
32.2
7.93
.72
.91
1.00
104.1 30.5
8.99
.74
.94
1.00
98.1
28.8
10.24
.77
.98
1.00
4800
2265 119.2 34.9
7.04
.75
.95
1.00
113.6
33.3
7.97
.77
.99
1.00
107.6 31.5
9.05
.80
1.00
1.00
101.9 29.9
10.30
.84
1.00
1.00
67
_
F
(19
_
C)
3200
1510 116.1 34.0
7.01
.53
.63
.76
111.0
32.5
7.93
.53
.65
.78
105.5 30.9
9.02
.54
.66
.81
99.3
29.1
10.28
.55
.68
.85
4000
1890 121.5 35.6
7.06
.55
.67
.84
115.9
34.0
8.01
.56
.69
.86
109.8 32.2
9.08
.57
.71
.90
103.2 30.2
10.33
.58
.74
.94
4800
2265 125.0 36.6
7.13
.57
.72
.91
119.5
35.0
8.05
.58
.75
.95
112.9 33.1
9.12
.59
.77
.98
106.3 31.2
10.35
.61
.81
1.00
71
_
F
(22
_
C)
3200
1510 122.7 36.0
7.10
.40
.51
.61
117.3
34.4
8.02
.41
.52
.62
111.3
32.6
9.07
.41
.52
.64
105.0 30.8
10.35
.41
.54
.66
4000
1890 128.4 37.6
7.16
.41
.53
.66
122.3
35.8
8.08
.42
.54
.67
116.1 34.0
9.16
.42
.56
.69
109.1 32.0
10.40
.43
.57
.72
4800
2265 132.4 38.8
7.23
.42
.56
.70
126.2
37.0
8.16
.43
.57
.72
119.5 35.0
9.21
.43
.59
.75
112.1 32.9
10.43
.44
.60
.78