TS 6 to 20 Ton R−410A Air Conditioners
ARI RATINGS
Gross
Cooling
Capacity
Btuh
Net
Cooling
Capacity
Btuh
EER
Integrated
Part
Load
Value
Indoor Coil or
Air Handler
Expansion
Device
TSA072S4S
6 TON
Air Handlers
68,300
66,000
10.2
− − −
2
CBX32M−060 (Multi−Position)
Factory TXV
71,800
69,000
10.2
− − −
3
CBX27UH−060 (Up−Flow / Horizontal)
Factory TXV
72,700
71,000
11.2
− − −
3
TAA072S4S (Up−Flow / Horizontal)
Factory TXV
Up−Flow Indoor Coils
71,800
69,000
10.5
− − −
2
CX34−62D−6F
Factory TXV
75,000
72,000
10.8
− − −
(2) CX34−43B/C−6F
Factory TXV
Horizontal Indoor Coils
70,100
68,000
10.3
− − −
2
CH33−62D−2F
1
91M02
TSA090S4S
7.5 TON
Air Handlers
91,800
89,000
11.2
− − −
3
TAA090S4S (Up−Flow / Horizontal)
Factory TXV
95,000
92,000
11.3
− − −
3
TAA120S4D (Up−Flow / Horizontal)
Factory TXV
Up−Flow Indoor Coils
92,200
89,000
10.8
− − −
2
(2) CX34−49C−6F
Factory TXV
Down−Flow Indoor Coils
90,800
87,000
10.6
− − −
2
(2) CR33−50/60C−F
1
91M02
Horizontal Indoor Coils
92,800
89,000
10.8
− − −
2
(2) CH33−49C−2F
1
91M02
(2) TSA090S4S
(2) 7.5 TON
Air Handlers
178,000
172,000
11.0
12.2
3
TAA180S4D (Up−Flow / Horizontal)
Factory TXV
TSA120S4S
10 TON
Air Handlers
117,100
113,000
11.2
− − −
3
TAA120S4D (Up−Flow / Horizontal)
Factory TXV
Up−Flow Indoor Coils
115,500
111,000
10.9
− − −
2
(2) CX34−62D−6F
Factory TXV
Down−Flow Indoor Coils
111,400
107,000
10.6
− − −
2
(2) CR33−50/60C−2F
1
91M02
Horizontal Indoor Coils
116,000
111,000
10.8
− − −
2
(2) CH33−62D−2F
1
91M02
(2) TSA120S4S
(2) 10 TON
Air Handlers
231,800
222,000
11.0
12.0
3
TAA240S4D (Up−Flow / Horizontal)
TSA120S4D (DUAL CIRCUIT)
10 TON
Air Handlers
119,700
115,000
11.2
11.8
3
TAA120S4D (Up−Flow / Horizontal)
Factory TXV
Up−Flow Indoor Coils
115,900
111,000
10.8
11.3
(2) CX34−60D−6F
Factory TXV
116,900
112,000
10.9
11.4
(2) CX34−62D−6F
Factory TXV
Down−Flow Indoor Coils
111,700
107,000
10.7
11.1
2
(2) CR33−50/60C−2F
1
91M02
Horizontal Indoor Coils
116,100
111,000
10.8
11.2
2
(2) CH33−62D−2F
1
91M02
NOTES − Net capacity includes indoor blower motor heat deduction. Gross capacity does not include indoor blower motor heat deduction.
Units with capacity of 65,000 Btuh or greater are certified in accordance with the ULE certification program which is based on ARI Standard 340/360: 95
_
F outdoor air
temperature, 80
_
F db/67
_
F wb entering evaporator air (minimum external duct static pressure) with 25 ft. of connecting refrigerant lines.
1
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
2
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation.
3
Blower control must be set for a time−off blower delay.