TS 6 to 20 Ton R−410A Air Conditioners
UNIT CLEARANCES − INCHES (MM)
TSA072 and TSA090
CONTROL
BOX ACCESS
See
NOTES
See
NOTES
See
NOTES
See
NOTES
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on
one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
(914 mm).
Clearance to one of the remaining two sides may be 12 in.
(305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between
two units.
48 in. (1219 mm) clearance required on top of unit.
TSA120 and TSA150
CONTROL
BOX ACCESS
See
NOTES
NOTES:
Service clearance of 30 in. (762 mm) must be main-
tained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
(914 mm).
Clearance to one of the remaining two sides may be 12
in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained be-
tween two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
See
NOTES
See
NOTES
TSA180 and TSA240
CONTROL
BOX ACCESS
See
NOTES
NOTES:
Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the
control box.
Clearance to one of the other three sides must be
36 in. (914 mm).
Clearance to one of the remaining two sides may
be 12 in. (305 mm) and the final side may be 6 in.
(152 mm).
A clearance of 24 in. (610 mm) must be main-
tained between two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
See
NOTES
See
NOTES