GUIDE SPECIFICATIONS

TS 6 to 12.5 Ton R−410A Air Conditioners

 / Page 29

  This Specification is for Lennox Industries T−Class

t

, 6 to 20 Ton, outdoor air conditioner split system

(TS series) units.  Revise specification section number and title below to suit project requirements,
specification practices and section content. Refer to CSI 

MasterFormat

 for other section numbers and

titles.

Optional text or text requiring a decision is indicated by 

bold brackets

 

[ ]

; delete text not required in final

copy of specification. Specifier Notes typically precede specification text; delete notes in final copy of
specification. Trade/brand names with appropriate symbols typically are used in Specifier Notes; symbols
are not used in specification text. Metric conversion, where used, is soft metric conversion.

SECTION 23 63 00

REFRIGERANT CONDENSERS

PART 1 GENERAL

1.01 SUMMARY

A. Section Includes: Split System Condensing Units.

Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and titles per CSI

MasterFormat

 and specifier’s practice.

B. Related Sections

Specifier Note: Article below may be omitted when specifying manufacturer’s proprietary products and
recommended installation. Retain Reference Article when specifying products and installation by an industry
reference standard. If retained, list standard(s) referenced in this section. Indicate issuing authority name,
acronym, standard designation and title. Establish policy for indicating edition date of standard referenced.
Conditions of the Contract or Division 1 References Section may establish the edition date of standards. This
article does not require compliance with standard, but is merely a listing of references used. Article below
should list only those industry standards referenced in this section. Retain only those reference standards to
be used within the text of this Section. Add and delete as required for specific project.

1.02 REFERENCES

A.

Air−Conditioning and Refrigeration Institute (ARI):

1.

ARI 270−95 Sound Rating of Outdoor Unitary Equipment.

2.

ARI 340/360 Commercial and Industrial Unitary Air−Conditioning and Heat Pump Equipment (ANSI
approved)

B.

Servicing Standards:

1.

National Electric Code (NEC).

2.

Underwriters Laboratories (UL).

3.

Canadian Electric Code (CEC).

C.

Units to be Department of Energy (DOE) rated

D.

ISO 9001, units manufactured to quality standard

E.

Meet Minimum EPACT 2005, and addendums, efficiency levels

 

Specifier Note: Article below should be restricted to statements describing design or performance requirements
and functional (not dimensional) tolerances of a complete system. Limit descriptions to composite and
operational properties required to link components of a system together and to interface with other systems.

1.03 SYSTEM DESCRIPTION

A.

Performance Requirements:

1.

Condensing Unit: [6, 7.5, 10, 12.5, 15 and 20 ton capacity].

2.

 Electrical Characteristics:

a.60 Hz.
b.3 phase.
c. Voltage:  

[208/230 V] [460 V] [575 V]

.

Specifier Note: Article below includes submittal of relevant data to be furnished by Contractor before, during or
after construction. Coordinate this article with Architect’s and Contractor’s duties and responsibilities in
Conditions of the Contract and Division 1 Submittal Procedures Section.

1.04 SUBMITTALS

A.

General: Submit listed submittals in accordance with Conditions of the Contract and Division 1 Submittal
Procedures.

Содержание T-CLASS TS Series

Страница 1: ...gn Sequence A 1st Generation B 2nd Generation Brand Family T T Class Product Line Unit Type S Split System Air Conditioner Nominal Cooling Capacity Tons 072 6 Tons 090 7 5 Tons 120 10 Tons 150 12 5 To...

Страница 2: ...e years in non residential applications All other covered components one year in non residential applications Refer to Lennox Equipment Limited Warranty certificate for specific details Approvals All...

Страница 3: ...ing pressure Manual reset Loss of Charge Switch Shuts off unit if liquid line pressure falls below setting Provides loss of charge and freeze up protection Automatic reset Hi Capacity Drier s Drier tr...

Страница 4: ...base pan is provided with this option Field Installed Coil Guards Heavy duty sheet metal and metal mesh enclosures protect coils from damage Field installed Hail Guards Heavy duty sheet metal and met...

Страница 5: ...ccessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1 C0S...

Страница 6: ...075 Watts 430 580 ELECTRICAL DATA Line voltage data 60 hz 3 phase 208 230V 460V 575V 208 230V 460V 575V 2 Maximum Overcurrent Protection amps 45 20 15 50 25 20 3 Minimum circuit ampacity 27 14 11 35 1...

Страница 7: ...60 hz 3 phase 208 230V 460V 575V 208 230V 460V 575V 2 Maximum Overcurrent Protection amps 70 40 25 50 25 20 3 Minimum circuit ampacity 43 24 18 41 21 15 Compressor No of Compressors 1 1 1 2 2 2 Rated...

Страница 8: ...575V 208 230V 460V 575V 208 230V 460V 575V 2 Maximum Overcurrent Protection amps 60 30 25 90 40 30 100 50 40 3 Minimum circuit ampacity 49 25 20 66 33 25 78 43 32 Compressor No of Compressors 2 2 2 2...

Страница 9: ...roller C0CTRL07AE1L 17M10 x x x x x x x NOTE The catalog and model numbers that appear here are for ordering field installed accessories only f Factory Installed with extended lead time X Field Instal...

Страница 10: ...9 2 2 CX34 62D 6F Factory TXV Down Flow Indoor Coils 111 400 107 000 10 6 2 2 CR33 50 60C 2F 1 91M02 Horizontal Indoor Coils 116 000 111 000 10 8 2 2 CH33 62D 2F 1 91M02 2 TSA120S4S 2 10 TON Air Handl...

Страница 11: ...clude indoor blower motor heat deduction Units with capacity of 65 000 Btuh or greater are certified in accordance with the ULE certification program which is based on ARI Standard 340 360 95_F outdoo...

Страница 12: ...ain tained on one of the sides adjacent to the control box Clearance to one of the other three sides must be 36 in 914 mm Clearance to one of the remaining two sides may be 12 in 305 mm and the final...

Страница 13: ...4 1149 REFRIGERANT LINE CONNECTIONS SEE DETAIL REFRIGERANT LINE CONNECTIONS DETAIL EE FF CONTROL BOX ACCESS COMPRESSOR COMPRESSOR CENTER OF GRAVITY INLET AIR INLET AIR DISCHARGE AIR BASE LIFTING HOLE...

Страница 14: ...60 1 8 1527 57 7 8 1470 COMPRESSOR BASE FRONT VIEW FORKLIFT SLOTS Both Sides CONTROL BOX ACCESS ELECTRICAL INLETS Above Refrigerant Lines TOP VIEW FF EE INLET AIR INLET AIR AA BB CC DD CENTER OF GRAVI...

Страница 15: ...OP VIEW FORKLIFT SLOTS Both Sides SIDE VIEW 88 3 4 2254 48 3 4 1238 3 1 2 89 45 1 4 1149 FF EE CENTER OF GRAVITY AA BB CC DD 3 3 4 95 6 1 2 165 BASE COMPRESSOR SUCTION LINE 2 LIQUID LINE 2 OUTDOOR FAN...

Страница 16: ..._F 29_C kBtuh kW 75_F 24_C 80_F 27_C 85_F 29_C 63_F 17_C 1920 905 69 2 20 3 4 84 68 82 97 66 0 19 3 5 37 69 85 99 62 5 18 3 5 97 70 87 1 00 58 7 17 2 6 65 72 91 1 00 2400 1135 72 5 21 2 4 85 72 90 1 0...

Страница 17: ...kBtuh kW 75_F 24_C 80_F 27_C 85_F 29_C 63_F 17_C 1920 905 72 1 21 1 4 86 67 82 97 68 9 20 2 5 39 68 84 1 00 65 3 19 1 5 99 70 87 1 00 61 3 18 0 6 68 72 91 1 00 2400 1135 76 0 22 3 4 88 71 89 1 00 72 4...

Страница 18: ...8 29 2 6 71 43 57 70 94 8 27 8 7 42 43 58 72 89 1 26 1 8 24 43 59 74 3600 1700 107 6 31 5 6 15 44 59 73 102 3 30 0 6 77 44 59 76 97 4 28 5 7 48 45 62 79 91 5 26 8 8 29 46 63 82 COOLING CAPACITY 2 TSA...

Страница 19: ...C 85_F 29_C kBtuh kW 75_F 24_C 80_F 27_C 85_F 29_C 63_F 17_C 2400 1135 86 1 25 2 5 73 68 81 96 82 2 24 1 6 36 69 83 98 78 3 22 9 7 08 70 86 1 00 73 8 21 6 7 91 72 89 1 00 3000 1415 89 9 26 3 5 80 72 8...

Страница 20: ...6 04 43 56 69 134 1 39 3 6 67 44 57 70 129 1 37 8 7 38 44 58 72 123 1 36 1 8 18 44 59 74 9600 4530 143 4 42 0 6 12 45 60 74 137 9 40 4 6 75 45 60 75 132 3 38 8 7 45 45 61 78 126 7 37 1 8 25 45 63 80...

Страница 21: ...24 6 36 5 7 30 44 58 71 119 5 35 0 8 10 45 59 72 113 7 33 3 9 01 45 60 74 107 3 31 4 10 04 45 62 77 4800 2265 128 5 37 7 7 37 45 61 75 122 9 36 0 8 17 46 62 77 116 8 34 2 9 07 46 63 80 110 2 32 3 10 1...

Страница 22: ...00 1890 132 4 38 8 7 22 41 54 67 126 5 37 1 8 15 41 56 69 119 4 35 0 9 22 42 57 71 112 1 32 9 10 45 43 58 75 4800 2265 136 5 40 0 7 29 42 58 73 129 9 38 1 8 21 43 59 75 122 7 36 0 9 27 43 60 78 115 1...

Страница 23: ...90 129 5 38 0 7 17 41 53 66 123 4 36 2 8 10 42 54 67 117 2 34 3 9 19 42 56 68 110 1 32 3 10 43 43 57 71 4800 2265 133 8 39 2 7 24 42 56 69 127 4 37 3 8 17 43 57 72 120 5 35 3 9 24 43 59 75 113 0 33 1...

Страница 24: ...0 69 3 20 3 2 81 41 52 62 66 7 19 5 3 17 41 52 63 64 0 18 8 3 58 41 53 65 60 9 17 8 4 04 42 54 66 4800 2265 71 8 21 0 2 84 42 54 66 69 1 20 3 3 20 42 54 67 66 1 19 4 3 61 42 55 68 63 0 18 5 4 07 43 56...

Страница 25: ...46 4 9 05 42 54 65 151 2 44 3 10 07 42 54 66 143 6 42 1 11 21 42 56 68 135 0 39 6 12 53 43 57 70 4800 2265 163 8 48 0 9 06 43 56 70 156 3 45 8 10 07 43 57 71 148 5 43 5 11 23 43 58 74 139 8 41 0 12 5...

Страница 26: ...2 55 67 85 0 24 9 4 08 43 56 69 81 7 23 9 4 54 43 57 70 78 0 22 9 5 03 43 58 72 6000 2830 91 0 26 7 3 69 43 58 72 87 7 25 7 4 09 43 59 73 84 3 24 7 4 54 44 60 75 80 5 23 6 5 05 45 61 77 COOLING CAPACI...

Страница 27: ...7 16 07 45 59 72 6000 2830 201 5 59 1 11 81 45 59 72 192 5 56 4 13 06 45 60 74 183 1 53 7 14 51 46 61 75 173 0 50 7 16 17 47 62 78 7200 3400 207 6 60 8 11 92 46 62 77 198 5 58 2 13 17 47 63 79 188 6 5...

Страница 28: ...3775 269 4 79 0 15 38 46 60 74 258 0 75 6 17 12 46 62 76 244 8 71 7 19 10 46 63 78 231 0 67 7 21 37 47 65 80 9600 4530 277 1 81 2 15 51 46 63 80 264 8 77 6 17 23 47 65 81 251 1 73 6 19 20 47 66 84 236...

Страница 29: ...the edition date of standards This article does not require compliance with standard but is merely a listing of references used Article below should list only those industry standards referenced in th...

Страница 30: ...e Include names and addresses of spare part suppliers 3 Provide brief description of unit with details of function operation control and component service 4 Commissioning Report Submit commissioning r...

Страница 31: ...teel b Pre painted finish c Refrigerant line connections to be located outside the unit d Control access e All controls factory wired 2 Compressor a Scroll Type b Resiliently mounted on rubber mounts...

Страница 32: ...written data including product technical bulletins product catalog installation instructions and product carton installation instructions 3 02 EXAMINATION A Site Verification of Conditions Verify sub...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installation and servic...

Отзывы: