TS 6 to 20 Ton R−410A Air Conditioners
/ Page 6
Specifications
6 − 7.5 TON
General
Data
Model No.
TSA072S4S
TSA090S4S
Nominal Size − Tons
6
7.5
Connections
(sweat)
Liquid line − in. (o.d)
(1) 5/8
(1) 5/8
Suction line − in. (o.d)
(1) 1−1/8
(1) 1−1/8
Refrigerant (R−410A)
Factory installed holding charge
1
Field provided charge with 25 ft. line set
11 lbs. 0 oz.
16 lbs. 0 oz.
Condenser
Coil
Net face area − sq. ft. Outer coil
29.3
29.3
Inner coil
− − −
28.4
Tube diameter − in. & no. of rows
3/8 − 1
3/8 − 2
Fins per inch
20
20
Condenser
Fan(s)
Diameter − in. & no. of blades
(1) 24 − 3
(1) 24 − 4
Motor hp
(1) 1/3
(1) 1/2
Total air volume − cfm
5100
5600
Rpm
1075
1075
Watts
430
580
ELECTRICAL DATA
Line voltage data − 60 hz − 3 phase
208/230V
460V
575V
208/230V
460V
575V
2
Maximum Overcurrent Protection (amps)
45
20
15
50
25
20
3
Minimum circuit ampacity
27
14
11
35
17
13
Compressor
No. of Compressors
1
1
1
1
1
1
Rated load amps
19
9.7
7.4
25
12.2
9
Locked rotor amps
123
62
50
164
100
78
Condenser
FanMotor
(1 phase)
No. of motors
1
1
1
1
1
1
Full load amps
2.4
1.3
1
3
1.5
1.2
Locked rotor amps
4.7
2.4
1.9
6
3
2.9
NOTE − Extremes of operating range are plus and minus 10% of line voltage.
1
Refer to the Lennox Refrigerant Piping Manual to determine refrigerant charge required with longer length refrigerant lines.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.