Page 56
Gas manifold pressure within
Check the following
1-
Does the unit have the correct
air orifice size? See table 28.
2
-Is the orifice fully seated tight
against the elbow ?
3
-Is the orifice damaged in any
way?
4
- Is the air inlet screen clear of
any obstruction ?
Correct any problems found.
Is ignition or resonance issue
resolved ?
Check Air Orifice
Troubleshooting is complete
Check Gas Manifold Pressure
Replace air orifice.
see table 3.
Check signal Pressure
Signal pressure within
Replace gas valve
Check the following
1-
. Vent /air intake pipe restriction.
2-
Plugged drain
3
- Plugged air inlet screen
4 -
Signal hoses to gas valve
for kinks, loose fit or plugging.
Correct any problems found.
Manifold pressure correct ?
Replace gas valve
No
Yes
Is ignition or resonance
issue resolved?
Yes
Troubleshooting is complete
No
Replace air orifice.
No
No
Yes
Troubleshooting Poor Ignition or Combustion Resonance Issues
No
Yes
Yes
FIGURE 49