background image

Printed in U.S.A.

        

440 04 4801 04 

      9/15/2018

SERVICE AND TECHNICAL SUPPORT MANUAL

Variable Speed Motor, Two

Stage

35” Tall, High Efficiency Condensing Gas Furnace

(F/G)9MVE

Save this manual for future reference.

Safety Labeling and Signal Words

DANGER, WARNING, CAUTION, and NOTE

The signal words 

DANGER, WARNING

,

CAUTION

,

 

and

 NOTE 

are used to identify levels of

hazard seriousness. The signal word

 DANGER 

is

only used on product labels to signify an immediate

hazard. The signal words 

WARNING

CAUTION

,

and 

NOTE

 will be used on product labels and

throughout this manual and other manual that may

apply to the product.

DANGER

 

 Immediate hazards which will result in

severe personal injury or death.

WARNING

 

 Hazards or unsafe practices which

could result in severe personal injury or death.

CAUTION 

 Hazards or unsafe practices which

may result in minor personal injury or product or

property damage.

NOTE 

 Used to highlight suggestions which will

result in enhanced installation, reliability, or

operation.

!

WARNING

Signal Words in Manuals

The signal word 

CAUTION

 is used throughout

this manual in the following manner:

!

CAUTION

Signal Words on Product Labeling

Signal words are used in combination with

colors and/or pictures or product labels.

The signal word 

WARNING

 is used throughout

this manual in the following manner:

Safety

alert symbol

When you see this symbol on the unit and in

instructions or manuals, be alert to the

potential for personal injury.

TABLE OF CONTENTS

START

UP, ADJUSTMENT, AND SAFETY CHECK

4

. . . . . . . . . . .

SETUP SWITCHES

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PRIME CONDENSATE TRAP WITH WATER

4

. . . . . . . . . . . . . . . . .

PURGE GAS LINES

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ADJUSTMENTS

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ADJUST TEMPERATURE RISE

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

ADJUST BLOWER OFF DELAY (HEAT MODE)

12

. . . . . . . . . . . . . .

ADJUST COOLING AIRFLOW

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ADJUST CONTINUOUS FAN AIRFLOW

12

. . . . . . . . . . . . . . . . . . . .

ADJUST THERMOSTAT HEAT ANTICIPATOR

14

. . . . . . . . . . . . . . .

CHECK SAFETY CONTROLS

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CHECKLIST

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

COOLING AND HEATING AIR DELIVERY - CFM

15

. . . . . . . . . . . . .

SERVICE AND MAINTENANCE PROCEDURES

17

. . . . . . . . . . . . .

ELECTRICAL CONTROLS AND WIRING

17

. . . . . . . . . . . . . . . . . . .

CLEANING AND/OR REPLACING AIR FILTER

19

. . . . . . . . . . . . . .

BLOWER MOTOR AND WHEEL MAINTENANCE

20

. . . . . . . . . . . .

CLEANING BURNERS AND FLAME SENSOR

21

. . . . . . . . . . . . . . .

SERVICING HOT SURFACE IGNITER

22

. . . . . . . . . . . . . . . . . . . . . .

FLUSHING COLLECTOR BOX AND DRAINAGE SYSTEM

23

. . . .

CLEANING CONDENSATE DRAIN AND TRAP

23

. . . . . . . . . . . . . .

CLEANING HEAT EXCHANGERS

23

. . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE LABEL

26

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

WIRING DIAGRAM

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING GUIDE 

 FLOW CHART

28

. . . . . . . . . . . . . .

SEQUENCE OF OPERATION

30

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PARTS REPLACEMENT INFORMATION GUIDE

35

. . . . . . . . . . . . .

PRODUCT NOMENCLATURE

36

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MODELS

(F/G)9MVE0401410A

(F/G)9MVE0401712A

(F/G)9MVE0601412A

(F/G)9MVE0601714A

(F/G)9MVE0801716A

(F/G)9MVE0802120A

(F/G)9MVE1002120A

(F/G)9MVE1202422A

Use of the AHRI Certified TM Mark indicates a

manufacturer’s participation in the program.

For verification of certification for individual

products, go to www.ahridirectory.org .

Содержание F9MVE Series

Страница 1: ...abels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential f...

Страница 2: ...l result in enhanced installation reliability or operation FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation perso...

Страница 3: ...in Connected Condensate Drain Trapped Manual Gas Shut off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Shade in Final Furnace Settings Below O N O...

Страница 4: ...l Setup Switches SW1 The furnace control has 8 setup switches that may be set to meet the application requirements To set these setup switches for the appropriate requirement 1 Remove blower door 2 Lo...

Страница 5: ...soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life WARNING Adjustments FIRE HAZ...

Страница 6: ...0 Btu cu ft Specific gravity 0 62 Therefore Orifice No 44 Furnace is shipped with No 44 orifices In this example all main burner orifices are the correct size and do not need to be changed to obtain p...

Страница 7: ...ease input rate Figure 3 Redundant Automatic Gas Control Valve 2 Stage without Tower Pressure Ports ON OFF Switch Regulator Seal Cap RegulatorAdjustment Regulator Seal Cap under Cap 1 2 NPT Outlet 1 8...

Страница 8: ...s warning could result in personal injury death and or property damage Manifold pressure tap set screw must be tightened or 1 8 in NPT pipe plug must be installed to prevent gas leaks WARNING c Tighte...

Страница 9: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48...

Страница 10: ...43 3 8 1 6 42 3 2 1 4 850 44 3 8 1 6 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 875 44 3 6 1 5 44 3 7 1 6 43 3 4 1 4 43 3 5 1 5 4000 900 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 1219 925 44 3 2 1 4 44 3 4 1...

Страница 11: ...re and airflow FURNACE DAMAGE HAZARD Failure to follow this caution may result in S Overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Short...

Страница 12: ...r off delay See Table 4 and Figure 4 Figure 5 Table 4 Blower Speed Taps DESIRED HEATING MODE BLOWER OFF DELAY SEC SETUP SWITCH SW1 7 and 8 POSITION 90 OFF OFF 120 ON OFF 150 OFF ON 180 ON ON Adjust Co...

Страница 13: ...r refer to unit wiring diagram TWN 1 CFM 2 3 4 5 6 7 8 SW2 CF AC SW2 1 Twining OFF Allows for selection of furnace Main OFF or Secondary ON when Twinned furnace setup is required See kit instructions...

Страница 14: ...can be established that limit is functioning properly and will operate if there is a restricted return air supply or motor failure If limit control does not function during this test cause must be de...

Страница 15: ...FF OFF ON 605 565 510 455 420 See note 4 OFF ON OFF 785 750 705 675 630 585 See note 4 OFF ON ON 955 920 895 860 825 785 755 720 685 650 ON OFF OFF 1135 1110 1080 1055 1020 990 935 880 825 745 ON OFF...

Страница 16: ...0 22 Clg Default OFF OFF OFF 2010 1960 1910 1850 1800 1750 1690 1645 1565 1480 Cooling SW2 OFF OFF ON 1015 805 645 550 480 See note 4 OFF ON OFF 1075 975 915 835 765 See note 4 OFF ON ON 1205 1135 105...

Страница 17: ...itioned air is discharged upward Since this furnace can be installed in any of the 4 positions shown in Figure 7 you must revise your orientation to component location accordingly Figure 7 Multipoise...

Страница 18: ...isconnecting the limit switch To retrieve Status Codes follow the procedure below 2 Turn Setup Switch SW1 1 ON 3 Manually close blower door switch 4 Control will flash up to 7 Status Codes 5 The last...

Страница 19: ...eason Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency...

Страница 20: ...balance will be affected 7 If greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on s...

Страница 21: ...following items must be performed by a qualified service technician If the burners develop an accumulation of light dirt or dust they may be cleaned by using the following procedure NOTE Use a back up...

Страница 22: ...the Hot Surface Igniter NOTE Use propane resistant pipe dope to prevent leaks Do not use Teflon tape 13 Install the gas pipe to the gas valve Figure 12 Igniter Position Side View L12F041 2 in 2 5 mm...

Страница 23: ...quired Verify a condensate trap gasket is included in the service kit or obtain one from your local distributor 1 Disconnect power at external disconnect fuse or circuit breaker 2 Turn off gas at exte...

Страница 24: ...wiring diagram and reconnect wires to flame rollout switch gas valve igniter and flame sensor 10 Turn on gas and electrical supplies to furnace 11 Check furnace operation through two complete heat op...

Страница 25: ...uart of anti freeze solution into the funnel tube Antifreeze should run through the collector box overfill condensate trap and flow to an open drain 8 Replace the rubber plug in the port on the collec...

Страница 26: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MVE Specifications subject to change without notice 440 04 4801 04 26 Figure 15 Service Label 340688 2 REV D...

Страница 27: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MVE Specifications subject to change without notice 27 440 04 4801 04 Figure 16 Wiring Diagram 340688 2 REV D...

Страница 28: ...t flashes When done put setup switch SW1 1 in the OFF position Was there a previous status code other than the heartbeat Go to section below for the status code that was flashed Does the control respo...

Страница 29: ...t check manifold pressure If OK check burner carryover and flame sensor location Clean flame sensor with fine steel wool and recheck current Nominal current is 4 0 to 6 0 microamps Is current near typ...

Страница 30: ...t high speed and the high heat pressure switch relay HPSR is de energized to close the NC contact When sufficient pressure is available the high heat pressure switch HPS closes and the high heat gas v...

Страница 31: ...tor BLWM will continue operating at cooling airflow for an additional 90 seconds Jumper Y Y2 to DHUM to reduce the cooling off delay to 5 seconds See Figure 4 b Two Stage Thermostat and Two Speed Cool...

Страница 32: ...eat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W W1 is energized along with Y1 or Y Y2 the furnace control...

Страница 33: ...801 04 Figure 20 Variable Speed Furnace with Single Stage Heat Pump Dual Fuel L09F026 NOTE 9 Figure 21 Variable Speed Furnace with Two Stage Heat Pump Dual Fuel L09F028 NOTE 9 Figure 22 Variable Speed...

Страница 34: ...stallation Instructions for additional information and setup procedure 4 When using a Humidity Sensing Thermostat set DEHUMIDIFY OPTIONS to H DE ENRGZD FOR DEHUM 5 Optional connection If wire is conne...

Страница 35: ...ector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation...

Страница 36: ...ed X ECM S Single stage T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low N...

Отзывы: