Page 5
BLOWER DATA
SL297UH040NV36B BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
886
905
+18%
825
859
+12%
802
819
+6%
769
770
Factory Default
688
736
–6%
634
678
–12%
635
605
–18%
547
553
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low
Medium-High
2
High
Low
Medium-Low
Medium-High
2
High
+
542
698
835
947
886
1034
1201
1320
Factory Default
462
634
735
855
808
949
1096
1248
–
413
534
678
779
734
868
987
1130
SL297UH060NV36B BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1106
1234
+18%
1047
1158
+12%
989
1110
+6%
940
1054
Factory Default
886
999
–6%
837
947
–12%
780
882
–18%
722
826
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low
Medium-High
2
High
Low
Medium-Low
Medium-High
2
High
+
611
739
843
949
879
1046
1212
1380
Factory Default
554
681
783
883
816
952
1107
1254
–
486
630
712
802
739
876
1006
1132
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 250 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 250 cfm.